Features

*  2-channel isolated barrier

*  24 V DC supply (Power Rail)

*  Input 2-wire SMART transmitters

*  Output 0/4 mA … 20 mA

*  Terminals with test points

*  Up to SIL 2 acc. to IEC 61508

Function of Pepperl+Fuchs KFD2-STC4-Ex2 SMART Transmitter Power Supply

*  This isolated barrier is used for intrinsic safety applications.

*  The device supplies 2-wire SMART transmitters in ahazardous area.

*  It transfers the analog input signal to the safe area as anisolated current value.

*  Digital signals may be superimposed on the input signal in thehazardous or safe area and are transferred bi-directionally.

*  If the HART communication resistance in the loop is too low,the internal resistance of 250 ? between terminals 8, 9and 11, 12 can be used.

*  Test sockets for the connection of HART communicators areintegrated into the terminals of the device

Specification of Pepperl+Fuchs KFD2-STC4-Ex2 SMART Transmitter Power Supply

Input 0/4 mA … 20 mA

Output 0/4 mA … 20 mA

General specifications

Signal type Analog input

Functional safety related parameters

Safety Integrity Level (SIL) SIL 2

Supply of Pepperl+Fuchs KFD2-STC4-Ex2 SMART Transmitter Power Supply

Connection Power Rail or terminals 14+, 15-

Rated voltage 20 … 35 V DC

Ripple within the supply tolerance

Power dissipation 1.8 W

Power consumption max. 2.7 W

Input of Pepperl+Fuchs KFD2-STC4-Ex2 SMART Transmitter Power Supply

Connection side field side

Connection terminals 1+, 3-; 4+, 6-

Input signal 0/4 … 20 mA

Available voltage ≥ 16 V at 20 mA, terminals 1+, 3

Output of Pepperl+Fuchs KFD2-STC4-Ex2 SMART Transmitter Power Supply

Connection side control side

Connection terminals 7-, 8+; 10-, 11+

Load 0 … 550 Ω at 20 mA

Output signal 0/4 … 20 mA (overload > 25 mA)

Ripple max. 50 μA rms

Transfer characteristics

Deviation at 20 °C (68 °F), 0/4 … 20 mA

≤ 10 μA incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage

Influence of ambient temperature 0.25 μA/K

Frequency range field side into the control side: band width with 1 Vpp signal 0 … 7.5 kHz (-3 dB)

safe area to hazardous area: band width with 1 VSS signal 0.3 … 7.5 kHz (-3 dB)

Settling time 200 μs

Rise time/fall time 20 μs

Galvanic isolation of Pepperl+Fuchs KFD2-STC4-Ex2 SMART Transmitter Power Supply

Output/power supply functional insulation, rated insulation voltage 50 V AC

Output/Output functional insulation, rated insulation voltage 50 V AC

Indicators/settings of Pepperl+Fuchs KFD2-STC4-Ex2 SMART Transmitter Power Supply

Display elements LED

Labeling space for labeling at the front

Directive conformity of Pepperl+Fuchs KFD2-STC4-Ex2 SMART Transmitter Power Supply

Electromagnetic compatibility 

Directive 2014/30/EU EN 61326-1:2013 (industrial locations)

Conformity of Pepperl+Fuchs KFD2-STC4-Ex2 SMART Transmitter Power Supply

Electromagnetic compatibility NE 21:2011

Degree of protection IEC 60529:2001

Protection against electrical shock UL 61010-1:2012

Ambient conditions

Ambient temperature -20 … 60 °C (-4 … 140 °F)

Mechanical specifications of Pepperl+Fuchs KFD2-STC4-Ex2 SMART Transmitter Power Supply

Degree of protection IP20

Connection screw terminals

Mass approx. 150 g

Dimensions 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , housing type B2

Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001

Data for application in connection with hazardous areas

EU-type examination certificate BAS 99 ATEX 7025 X

Marking Ex-Hexagon II (1)G [Ex ia Ga] IIC , Ex-Hexagon II (1)D [Ex ia Da] IIIC , Ex-Hexagon I (M1) [Ex ia Ma] I

Input [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I

Voltage 25.2 V

Current 93 mA

Power 0.586 W

Supply of Pepperl+Fuchs KFD2-STC4-Ex2 SMART Transmitter Power Supply

Maximum safe voltage 250 V (Attention! The rated voltage can be lower.)

Certificate TüV 99 ATEX 1499 X

Marking Ex-Hexagon II 3G Ex nA II T4 [device in zone 2]

Galvanic isolation 

Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V

Input/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V

Directive conformity 

Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010

International approvals

UL approval of Pepperl+Fuchs KFD2-STC4-Ex2 SMART Transmitter Power Supply

Control drawing 116-0428 (cULus)

IECEx approval IECEx BAS 04.0015X

IECEx CML 15.0055X

Approved for [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I

Ex nA IIC T4 Gc

Ordering Models of Pepperl+Fuchs KFD2-STC4-Ex2 SMART Transmitter Power Supply

KFD2-STC5-Ex1

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/4 mA … 20 mA current sink/current source, Terminals with test points, Up to SIL 2 acc. to IEC 61508

KCD2-STC-1.2O

SMART Transmitter Power Supply

1-channel signal conditioner, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA … 20 mA or 0/1 V … 5 V, Terminal blocks with test sockets, Up to SIL 2 acc. to IEC 61508

KCD2-STC-Ex1

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA … 20 mA or 1 V … 5 V, Housing width 12.5 mm, Up to SIL 2 acc. to IEC 61508

KCD2-STC-Ex1.2O

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA … 20 mA or 0/1 V … 5 V, Terminal blocks with test sockets, Up to SIL 2 acc. to IEC 61508

KCD2-STC-Ex1.ES

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA … 20 mA or 1 V … 5 V, Sink or source mode, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 3 acc. to IEC 61508

KCD2-STC-Ex1.SP

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA … 20 mA or 1 V … 5 V, Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC 61508

KFA6-STR-1.24.4

Power Supply

115/230 V AC supply, Output 24 V DC, 4 A, Fused output, Power Rail connection

KFD0-CS-1.50

Repeater

1-channel signal conditioner, 24 V DC supply (loop powered), Current input/output 4 mA … 20 mA, transmitter power supply, Accuracy 0.1 %, Reverse polarity protection, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system

KFD0-CS-2.50

Repeater

2-channel signal conditioner, 24 V DC supply (loop powered), Current input/output 4 mA … 20 mA, transmitter power supply, Accuracy 0.1 %, Reverse polarity protection, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system

KFD0-CS-Ex1.50P

Repeater

1-channel isolated barrier, 24 V DC supply (loop powered), Current input/output 4 mA … 20 mA, transmitter power supply, Accuracy 0.1 %, Reverse polarity protection, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system

KFD0-CS-Ex1.51P

Current Driver/Repeater

1-channel isolated barrier, 24 V DC supply (loop powered), Current input/output 0 mA … 40 mA, I/P or transmitter power supply, Accuracy 1 %, Reverse polarity protection, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system

KFD0-CS-Ex2.50P

Repeater

2-channel isolated barrier, 24 V DC supply (loop powered), Current input/output 4 mA … 20 mA, transmitter power supply, Accuracy 0.1 %, Reverse polarity protection, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system

KFD0-CS-Ex2.51P

Current Driver/Repeater

2-channel isolated barrier, 24 V DC supply (loop powered), Current input/output 0 mA … 40 mA, I/P or transmitter power supply, Accuracy 1 %, Reverse polarity protection, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system

KFD2-STC3-Ex1

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), 2-wire SMART transmitter, Output 4 mA … 20 mA, SMART capable up to 40 kHz (-1dB), Suitable for Honeywell DE protocol, Terminals with test points

KFD2-STC4-Ex2-Y1

SMART Transmitter Power Supply, Output Current Sink

2-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire SMART transmitters, Output 0/4 mA … 20 mA current sink, Terminal blocks with test sockets, Up to SIL 2 acc. to IEC 61508

KFD2-STC5-Ex1

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/4 mA … 20 mA current sink/current source, Terminals with test points, Up to SIL 2 acc. to IEC 61508

KFD2-STC5-Ex1.2O.H

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA … 20 mA, current sink/current source, Terminals with test points, High field voltage 17 V DC, Up to SIL 3 acc. to IEC 61508

KCD2-STC-Ex1.2O.DE

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA … 20 mA or 0/1 V … 5 V, Terminal blocks with test sockets, Up to SIL 2 acc. to IEC 61508

KCD2-STC-Ex1.2O.ES

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA … 20 mA or 0/1 V … 5 V, Terminal blocks with test sockets, Up to SIL 3 acc. to IEC 61508

KCD2-STC-Ex1.ES.SP

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA … 20 mA or 1 V … 5 V, Sink or source mode, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 3 acc. to IEC 61508

KFD0-CS-2.51P

Current Driver/Repeater

2-channel signal conditioner, 24 V DC supply (loop powered), Current input/output 0 mA … 40 mA, I/P or transmitter power supply, Accuracy 1 %, Reverse polarity protection, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system

KFD0-SCS-1.55

SMART Current Driver/Repeater

1-channel signal conditioner, 24 V DC supply (loop powered), Current input/output 4 mA … 20 mA, HART I/P or transmitter power supply, Low voltage drop, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system

KFD2-HLC-Ex1.D.4S

HART Loop Converter

1-channel isolated barrier, 24 V DC supply (Power Rail), HART field device input with transmitter power supply, Usable as signal splitter (1 input and several outputs), 4 relay contact outputs (NO contact), 3 analog outputs 4 mA … 20 mA, Sink and source mode output, Configurable by keypad

KFD2-STC4-Ex1.2O-Y1

SMART Transmitter Power Supply, Output Current Sink

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA … 20 mA, current sink, Terminal blocks with test sockets, Up to SIL 3 acc. to IEC 61508

KFD2-STV4-Ex1-2

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/2 V … 10 V, Terminals with test points, Up to SIL 2 acc. to IEC 61508

KFD2-STV4-Ex1.2O-1

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Signal splitter (1 input and 2 outputs), Dual output 0/1 V … 5 V, Terminal blocks with test sockets, Up to SIL 3 acc. to IEC 61508

KFD2-STV4-Ex2-1

SMART Transmitter Power Supply

2-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire SMART transmitters, Output 0/1 V … 5 V, Terminals with test points, Up to SIL 2 acc. to IEC 61508

KFD2-STV4-Ex2-2

SMART Transmitter Power Supply

2-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire SMART transmitters, Output 0/2 V … 10 V, Terminals with test points, Up to SIL 2 acc. to IEC 61508

KFD2-STV5-Ex1-1

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/1 V … 5 V, Terminals with test points, Up to SIL 2 acc. to IEC 61508

KLD2-FBPS-1.12.220

Fieldbus Power Supply

Output: 12 … 13 V/220 mA, For battery or solar-powered applications, For demanding environmental conditions , Installation in Zone 2/Class I, Div. 2, For FOUNDATION Fieldbus H1

Ordering Codes of Pepperl+Fuchs KFD2-STC4-Ex2 SMART Transmitter Power Supply

We are specialized in intelligent instruments, including : Transmitters, Flowmeters, Analyzers,Communicators, Safety Barriers, Sensors,Gas Detectors, PLC(DCS), Multimeters, Calibrators, Communicators, Recorder, Inverters, Positioners, Valves, Soft Starters, Circuit Breakers, Contactors, Rail Switches, Power Supply, HMI, Terminal Block, Relay etc.