Product Features of Pepperl+Fuchs KFD0-CC-1 Current Voltage Converters

– Current/Voltage Converter KFD0-CC-1

– 1-channel signal conditioner

– 24 V DC supply (loop powered)

– Current or voltage input

– Output: 4 … 20 mA

– Potentiometer or DIP switch selectable ranges

– Line fault detection (LFD)

Technical Information of Pepperl+Fuchs KFD0-CC-1 Current Voltage Converter KFD0-CC-1 Safety Barriers

General specifications of Pepperl+Fuchs KFD0-CC-1 Current Voltage Converters

Signal type Analog input

Supply

Rated voltage 12 … 35 V DC loop powered

Power dissipation 0.4 W

Input of Pepperl+Fuchs KFD0-CC-1 Current Voltage Converters

Connection side field side

Connection terminals 1+, 2-

Current range 0 … 20 mA , load ≤ 50 Ω

Voltage range 0 … 10 V , load ≥ 100 kΩ

Output of Pepperl+Fuchs KFD0-CC-1 Current Voltage Converters

Connection side control side

Connection terminals 9+, 8-

Load (U -12 V) / 0.02 A

Current output 4 … 20 mA , limited to ≤ 35 mA

Fault signal downscaling ≤ 3 mA

Transfer characteristics of Pepperl+Fuchs KFD0-CC-1 Current Voltage Converters

Deviation 

After calibration 0.1 % of full-scale value

Temperature effect span: 0.050 % of span /K ; zero point: 0.060 % of span /K

Linearization ≤ 0.04 % of full-scale value

Influence of supply voltage 6.5 ppm/V

Rise time 250 ms

Galvanic isolation of Pepperl+Fuchs KFD0-CC-1 Current Voltage Converters

Input/Output safe isolation according to EN 50178, rated insulation voltage 253 Veff

Indicators/settings of Pepperl+Fuchs KFD0-CC-1 Current Voltage Converters

Control elements DIP-switch

potentiometer

Configuration via DIP switches

via potentiometer

Labeling space for labeling at the front

Directive conformity of Pepperl+Fuchs KFD0-CC-1 Current Voltage Converters

Electromagnetic compatibility 

Directive 2014/30/EU EN 61326-1:2013 (industrial locations)

Conformity of Pepperl+Fuchs KFD0-CC-1 Current Voltage Converters

Insulation coordination EN 50178

Galvanic isolation EN 50178

Degree of protection IEC 60529

Ambient conditions of Pepperl+Fuchs KFD0-CC-1 Current Voltage Converters

Ambient temperature -20 … 70 °C (-4 … 158 °F)

Mechanical specifications of Pepperl+Fuchs KFD0-CC-1 Current Voltage Converters

Degree of protection IP20

Connection screw terminals

Mass approx. 100 g

Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2

Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001

Ordering Codes of Pepperl+Fuchs KFD0-CC-1 Current Voltage Converters

Ordering Models of Pepperl+Fuchs KFD0-CC-1 Current Voltage Converters

KFA6-STR-1.24.500

Power Supply

115/230 V AC supply, Output 24 V DC, 500 mA, Electronic short circuit protection, Power Rail connection

KFD0-SCS-Ex1.55

SMART Current Driver/Repeater

1-channel isolated barrier, 24 V DC supply (loop powered), Current input/output 4 mA … 20 mA, HART I/P or transmitter power supply, Low voltage drop, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508, Rated voltage: loop powered, Explosion protection: Ex protection, Transfer direction: to the field / to the control system

KFD2-CRG2-1.D

Transmitter Power Supply

1-channel signal conditioner, 24 V DC supply (Power Rail), Input 2-wire and 3-wire transmitters and 2-wire current sources, Output 0/4 mA … 20 mA, 2 relay contact outputs, Adjustable energized/de-energized delay, Programmable high/low alarm, Linearization function (max 20 points), Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508/IEC 61511

KFD2-CRG2-Ex1.D

Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire transmitters and 2-wire current sources, Output 0/4 mA … 20 mA, 2 relay contact outputs, Adjustable energized/de-energized delay, Programmable high/low alarm, Linearization function (max 20 points), Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508/IEC 61511

KFD2-HLC-Ex1.D

HART Loop Converter

1-channel isolated barrier, 24 V DC supply (Power Rail), HART field device input with transmitter power supply, Usable as signal splitter (1 input and several outputs), 3 analog outputs 4 mA … 20 mA, Sink and source mode output, Configurable by keypad

KFD2-HLC-Ex1.D.2W

HART Loop Converter

1-channel isolated barrier, 24 V DC supply (Power Rail), HART field device input with transmitter power supply, Usable as signal splitter (1 input and several outputs), 2 relay contact outputs (change-over contacts), 3 analog outputs 4 mA … 20 mA, Sink and source mode output, Configurable by keypad

KFD2-STC5-1

SMART Transmitter Power Supply

1-channel signal conditioner, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/4 mA … 20 mA current sink/current source, Terminals with test points, Up to SIL 2 acc. to IEC 61508

KFD2-STC5-1.2O

SMART Transmitter Power Supply

1-channel signal conditioner, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA … 20 mA, current sink/current source, Terminals with test points, Up to SIL 3 acc. to IEC 61508

KFD2-STC5-2

SMART Transmitter Power Supply

2-channel signal conditioner, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/4 mA … 20 mA current sink/current source, Terminals with test points, Up to SIL 2 acc. to IEC 61508

KFD2-STC5-Ex1.2O

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA … 20 mA, current sink/current source, Terminals with test points, Up to SIL 3 acc. to IEC 61508

KFD2-STC5-Ex1.H

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/4 mA … 20 mA current sink/current source, Terminals with test points, High field voltage 17 V DC, Up to SIL 2 acc. to IEC 61508

KFD2-STC5-Ex2

SMART Transmitter Power Supply

2-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/4 mA … 20 mA current sink/current source, Terminals with test points, Up to SIL 2 acc. to IEC 61508

KFU8-CRG2-1.D

Transmitter Power Supply

1-channel signal conditioner, Universal usage at different power supplies, Input 2-wire and 3-wire transmitters and 2-wire current sources, Output 0/4 mA … 20 mA, 2 relay contact outputs, Adjustable energized/de-energized delay, Programmable high/low alarm, Linearization function (max 20 points), Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508/IEC 61511

KFU8-CRG2-Ex1.D

Transmitter Power Supply

1-channel isolated barrier, Universal usage at different power supplies, Input 2-wire and 3-wire transmitters and 2-wire current sources, Output 0/4 mA … 20 mA, 2 relay contact outputs, Adjustable energized/de-energized delay, Programmable high/low alarm, Linearization function (max 20 points), Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508/IEC 61511

KFU8-VCR-1

Transmitter Power Supply/Converter

1-channel signal conditioner, Universal usage at different power supplies, Input 2-wire and 3-wire transmitters, current and voltage sources, Current and voltage output, Rated voltage: 19 … 90 V DC / 48 … 253 V AC

KLD2-FBPS-1.25.360

Fieldbus Power Supply

Output: 25 … 27 V/360 mA, For most fieldbus applications, High-power trunk for high device count and long cable lengths, Installation in Zone 2/Class I, Div. 2, For FOUNDATION Fieldbus H1

KFD2-STC5-Ex1

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/4 mA … 20 mA current sink/current source, Terminals with test points, Up to SIL 2 acc. to IEC 61508

KCD2-STC-1.2O

SMART Transmitter Power Supply

1-channel signal conditioner, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA … 20 mA or 0/1 V … 5 V, Terminal blocks with test sockets, Up to SIL 2 acc. to IEC 61508

KCD2-STC-Ex1

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA … 20 mA or 1 V … 5 V, Housing width 12.5 mm, Up to SIL 2 acc. to IEC 61508

KCD2-STC-Ex1.2O

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA … 20 mA or 0/1 V … 5 V, Terminal blocks with test sockets, Up to SIL 2 acc. to IEC 61508

KCD2-STC-Ex1.ES

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA … 20 mA or 1 V … 5 V, Sink or source mode, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 3 acc. to IEC 61508

KCD2-STC-Ex1.SP

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA … 20 mA or 1 V … 5 V, Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC 61508

KFA6-STR-1.24.4

Power Supply

115/230 V AC supply, Output 24 V DC, 4 A, Fused output, Power Rail connection

KFD0-CS-1.50

Repeater

1-channel signal conditioner, 24 V DC supply (loop powered), Current input/output 4 mA … 20 mA, transmitter power supply, Accuracy 0.1 %, Reverse polarity protection, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system

KFD0-CS-2.50

Repeater

2-channel signal conditioner, 24 V DC supply (loop powered), Current input/output 4 mA … 20 mA, transmitter power supply, Accuracy 0.1 %, Reverse polarity protection, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system

KFD0-CS-Ex1.50P

Repeater

1-channel isolated barrier, 24 V DC supply (loop powered), Current input/output 4 mA … 20 mA, transmitter power supply, Accuracy 0.1 %, Reverse polarity protection, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system

KFD0-CS-Ex1.51P

Current Driver/Repeater

1-channel isolated barrier, 24 V DC supply (loop powered), Current input/output 0 mA … 40 mA, I/P or transmitter power supply, Accuracy 1 %, Reverse polarity protection, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system

KFD0-CS-Ex2.50P

Repeater

2-channel isolated barrier, 24 V DC supply (loop powered), Current input/output 4 mA … 20 mA, transmitter power supply, Accuracy 0.1 %, Reverse polarity protection, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system

KFD0-CS-Ex2.51P

Current Driver/Repeater

2-channel isolated barrier, 24 V DC supply (loop powered), Current input/output 0 mA … 40 mA, I/P or transmitter power supply, Accuracy 1 %, Reverse polarity protection, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system

KFD2-STC3-Ex1

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), 2-wire SMART transmitter, Output 4 mA … 20 mA, SMART capable up to 40 kHz (-1dB), Suitable for Honeywell DE protocol, Terminals with test points

KFD2-STC4-Ex2-Y1

SMART Transmitter Power Supply, Output Current Sink

2-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire SMART transmitters, Output 0/4 mA … 20 mA current sink, Terminal blocks with test sockets, Up to SIL 2 acc. to IEC 61508

KFD2-STC5-Ex1

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/4 mA … 20 mA current sink/current source, Terminals with test points, Up to SIL 2 acc. to IEC 61508

KFD2-STC5-Ex1.2O.H

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA … 20 mA, current sink/current source, Terminals with test points, High field voltage 17 V DC, Up to SIL 3 acc. to IEC 61508

KCD2-STC-Ex1.2O.DE

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA … 20 mA or 0/1 V … 5 V, Terminal blocks with test sockets, Up to SIL 2 acc. to IEC 61508

KCD2-STC-Ex1.2O.ES

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA … 20 mA or 0/1 V … 5 V, Terminal blocks with test sockets, Up to SIL 3 acc. to IEC 61508

KCD2-STC-Ex1.ES.SP

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA … 20 mA or 1 V … 5 V, Sink or source mode, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 3 acc. to IEC 61508

KFD0-CS-2.51P

Current Driver/Repeater

2-channel signal conditioner, 24 V DC supply (loop powered), Current input/output 0 mA … 40 mA, I/P or transmitter power supply, Accuracy 1 %, Reverse polarity protection, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system

KFD0-SCS-1.55

SMART Current Driver/Repeater

1-channel signal conditioner, 24 V DC supply (loop powered), Current input/output 4 mA … 20 mA, HART I/P or transmitter power supply, Low voltage drop, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system

KFD2-HLC-Ex1.D.4S

HART Loop Converter

1-channel isolated barrier, 24 V DC supply (Power Rail), HART field device input with transmitter power supply, Usable as signal splitter (1 input and several outputs), 4 relay contact outputs (NO contact), 3 analog outputs 4 mA … 20 mA, Sink and source mode output, Configurable by keypad

KFD2-STC4-Ex1.2O-Y1

SMART Transmitter Power Supply, Output Current Sink

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA … 20 mA, current sink, Terminal blocks with test sockets, Up to SIL 3 acc. to IEC 61508

KFD2-STV4-Ex1-2

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/2 V … 10 V, Terminals with test points, Up to SIL 2 acc. to IEC 61508

KFD2-STV4-Ex1.2O-1

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Signal splitter (1 input and 2 outputs), Dual output 0/1 V … 5 V, Terminal blocks with test sockets, Up to SIL 3 acc. to IEC 61508

KFD2-STV4-Ex2-1

SMART Transmitter Power Supply

2-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire SMART transmitters, Output 0/1 V … 5 V, Terminals with test points, Up to SIL 2 acc. to IEC 61508

KFD2-STV4-Ex2-2

SMART Transmitter Power Supply

2-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire SMART transmitters, Output 0/2 V … 10 V, Terminals with test points, Up to SIL 2 acc. to IEC 61508

KFD2-STV5-Ex1-1

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/1 V … 5 V, Terminals with test points, Up to SIL 2 acc. to IEC 61508

KLD2-FBPS-1.12.220

Fieldbus Power Supply

Output: 12 … 13 V/220 mA, For battery or solar-powered applications, For demanding environmental conditions , Installation in Zone 2/Class I, Div. 2, For FOUNDATION Fieldbus H1

We are specialized in intelligent instruments, including : Transmitters, Flowmeters, Analyzers,Communicators, Safety Barriers, Sensors,Gas Detectors, PLC(DCS), Multimeters, Calibrators, Communicators, Recorder, Inverters, Positioners, Valves, Soft Starters, Circuit Breakers, Contactors, Rail Switches, Power Supply, HMI, Terminal Block, Relay etc.