MTL4581 MTL5581 MILLIVOLT/THERMOCOUPLE ISOLATOR
Overview of MTL4581 MTL5581 MILLIVOLT/THERMOCOUPLE ISOLATOR
MTL4581 – MTL5581 MILLIVOLT/THERMOCOUPLE ISOLATOR for low-level signals
The MTLx581 takes a low-level dc signal from a voltage source in a hazardous area, isolates it, and passes it to a receiving instrument located in the safe area. The module is intended for use with thermocouples utilising external cold-junction compensation. A switch enables or disables the safety drive in the event of thermocouple burnout or cable breakage, a second switch permits the selection of upscale or downscale operation as appropriate.
Features
* Compact modular design with DIN rail mounting
* High packing density
* Single and multi-channel I/O modules
* 3-port isolation with low power dissipation
* Compatible with MTL5000
Technical Specification of MTL4581 MTL5581 MILLIVOLT/THERMOCOUPLE ISOLATOR
See also common specification
Number of channels
One
Signal source
Any dc millivolt source
Location of millivolt source
Zone 0, IIC, T4–T6 hazardous area if suitably certified
Div. 1, Group A, hazardous location
Input and output signal range
0 to ± 50mV, overrange to ± 55mV
Maximum lead resistance 600Ω
Output resistance
60Ω nominal
Transfer accuracy@20°C
Linearity and repeatability < 0.05% of reading or ± 5μV,
whichever is the greater
Temperature drift
< 2μV/°C, maximum
Response time
Settles to within 10% of final value within 150μs
Frequency response
dc to 4kHz nominal
Safety drive on THC burnout
Two switches enable or disable the safety drive and select
upscale or downscale operation
LED indicator
Green: power indication
Power requirement, Vs
30mA max, 20V dc to 35V dc
Power dissipation within unit
0.7W typical at 24V
0.91W at 35V
Safety description
Terminals 1 to 2
Non-energy-storing apparatus ≤ 1.5V, ≤ 0.1A and ≤ 25mW; can
be connected without further certification into any IS loop with an
open-circuit voltage <28V
Attribute Value
Input Type Voltage
Output Type Voltage
Signal Conditioner Type Isolation
Input Range 0 → ±5 mV
Output Range ±55 mV
Mounting Type DIN Rail
Sensor Compatibility Thermocouple
Minimum Operating Temperature -20°C
Maximum Operating Temperature +60°C
Series MTL5000
Number of Channels 1
Module Type Millivolt/Thermocouple Isolator
Operating Temperature Range -20 → +60 °C
Termination Cable
MTL4500 Series Barriers MTL4581 MTL5581 MILLIVOLT/THERMOCOUPLE ISOLATOR
MTL4581 MTL5581 MILLIVOLT/THERMOCOUPLE ISOLATOR
MTL4581 MTL5581 MILLIVOLT/THERMOCOUPLE ISOLATOR
MTL4581 MTL5581 MILLIVOLT/THERMOCOUPLE ISOLATOR
MTL4581 MTL5581 MILLIVOLT/THERMOCOUPLE ISOLATOR
MTL4581 MTL5581 MILLIVOLT/THERMOCOUPLE ISOLATOR
MTL4581 MTL5581 MILLIVOLT/THERMOCOUPLE ISOLATOR
MTL4581 MTL5581 MILLIVOLT/THERMOCOUPLE ISOLATOR
MTL4581 MTL5581 MILLIVOLT/THERMOCOUPLE ISOLATOR
We are specialized in intelligent instruments, including : Transmitters, Flowmeters, Analyzers,Communicators, Safety Barriers, Sensors,Gas Detectors, PLC(DCS), Multimeters, Calibrators, Communicators, Recorder, Inverters, Positioners, Valves, Soft Starters, Circuit Breakers, Contactors, Rail Switches, Power Supply, HMI, Terminal Block, Relay etc.