Pepperl+Fuchs KFU8-DW-1.D Rotation Speed Monitors


Product Features of Pepperl+Fuchs KFU8-DW-1.D Rotation Speed Monitors

Rotation Speed Monitor KFU8-DW-1.D

Speed monitoring up to 40 kHz
1 pre-select value with relay output and LED indicator
2-, 3-, 4-wire and NAMUR sensors as well as rotary encoder connectable
Start-up delay
Menu driven operation via 4 front keys
Period measurement
Output signal can be inverted
Display devices can be set between 0.1 … 2.5 sec.
Technical Specification of Pepperl+Fuchs KFU8-DW-1.D Rotation Speed Monitors

Product Description of Pepperl+Fuchs KFU8-DW-1.D Rotation Speed Monitors

Rotation Speed Monitor

Functional safety related parameters of Pepperl+Fuchs KFU8-DW-1.D Rotation Speed Monitors

MTTFd 100 a

Supply of Pepperl+Fuchs KFU8-DW-1.D Rotation Speed Monitors

Rated voltage 200 … 230 V AC ; 100 … 130 V AC; 50/60 Hz
20 VDC … 30 VDC
Fusing external fusing 4 A
Power consumption AC: < 5 VA
DC: < 5 W

Input 1 of Pepperl+Fuchs KFU8-DW-1.D Rotation Speed Monitors

Connection terminals 8-, 9+

Connectable sensor types NAMUR sensors according to DIN EN 60947-5-6
Open loop voltage 8.2 V DC
Short-circuit current 6.5 mA
Switching point 1.2 … 2.1 mA Switching hysteresis approx. 0.2 mA
Input frequency 0.002 … 10000 Hz, pulse length/duration: ≥ 20µs
Impedance 1.2 kΩ

Input 2 of Pepperl+Fuchs KFU8-DW-1.D Rotation Speed Monitors

Switching point high: 16 … 30 V DC; max.10 mA due to integrated constant current sink; Ri ≅ 3 kΩ
low: 0 … 6 V DC
Input frequency 0.002 … 40000 Hz, pulse length/duration: ≥ 12µs
Connection terminals 7+, 13- sensor supply
terminals 14, 15 NPN/PNP input (galvanically isolated)
Connectable sensor types Two, three, or four-wire proximity switch, incremental rotary encoder, or externally generated pulses 16 … 30 V
Sensor supply 19 … 28 V DC non-stabilised; ≤ 30 mA short-circuit protected

Input 3 of Pepperl+Fuchs KFU8-DW-1.D Rotation Speed Monitors

Start-up override Triggering by external signal 16 … 30 V or Place jumper between terminals 2/3 or by switching on supply voltage (terminal 2 and terminal 3 permanently bridged)
Jumpering time 0.1 … 999.9 s (External trigger signal)

Output of Pepperl+Fuchs KFU8-DW-1.D Rotation Speed Monitors

Relay 1 changeover contact
NO, NC, COM
Sensor supply 24 V DC ± 10 %, 30 mA , short-circuit protected
Contact loading 250 V AC/2 A/ cos φ ≥ 0.7
40 V DC/2 A
Delay ≤ 20 ms (incl. calculation time)
Mechanical life ≥ 30.000.000 switching cycles

Transfer characteristics of Pepperl+Fuchs KFU8-DW-1.D Rotation Speed Monitors

Changing interval 5 ms (Internal processing time)
Time delay before availability ≤ 400 ms
Measuring error 0 … 40000 Hz: ≤ ±0,10%
Display: ±1 digit
Timer function ON-delay, OFF-delay, one shot, pulse extension
Time 0 … 999.9 s ; mode of operation reversible
Standard conformity of Pepperl+Fuchs KFU8-DW-1.D Rotation Speed Monitors

Electromagnetic compatibility acc. to EN 50081-2 / EN 50082-2

Ambient conditions of Pepperl+Fuchs KFU8-DW-1.D Rotation Speed Monitors

Ambient temperature -25 … 40 °C (-13 … 104 °F)
Storage temperature -40 … 85 °C (-40 … 185 °F)
Relative humidity max. 80 %, not condensing
Altitude 0 … 2000 m
Operating conditions The device has only to be used in an indoor area.

Mechanical specifications of Pepperl+Fuchs KFU8-DW-1.D Rotation Speed Monitors

Connection assembly Caution: Please be aware that the device may only be connected to a switchable power supply. The switch or circuit breaker must be easy to reach and identified as the separator for the device.
Degree of protection IP20
Connection coded, removable terminals , max. core cross section 0.34 … 2.5 mm2
Construction type modular terminal housing in Makrolon, System KF
For use in the switch cabinet/switch cabinet module
Mounting snap-on to 35 mm standard rail or screw fixing

Classifications of Pepperl+Fuchs KFU8-DW-1.D Rotation Speed Monitors

System Classcode
ECLASS 11.0 27210904
ECLASS 10.0.1 27210904
ECLASS 9.0 27210904
ECLASS 8.0 27210904
ECLASS 5.1 27210904
ETIM 8.0 EC002918
ETIM 7.0 EC002918
ETIM 6.0 EC002918
ETIM 5.0 EC002918
UNSPSC 12.1 39121007

Similar Models of Pepperl+Fuchs KFU8-DW-1.D Rotation Speed Monitors
KFA6-DWB-Ex1.D
Rotation Speed Monitor
1-channel isolated barrier, 230 V AC supply, Dry contact or NAMUR inputs, Input frequency 1 mHz … 5 kHz, 2 relay contact outputs, Start-up override, Configurable by keypad, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508/IEC 61511
KFD2-DWB-1.D
Rotation Speed Monitor
1-channel signal conditioner, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Input frequency 1 mHz … 12 kHz, 2 relay contact outputs, Start-up override, Configurable by keypad, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508/IEC 61511
KFD2-DWB-Ex1.D
Rotation Speed Monitor
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Input frequency 1 mHz … 5 kHz, 2 relay contact outputs, Start-up override, Configurable by keypad, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508/IEC 61511
KFU8-DW-1.D
Rotation Speed Monitor
Speed monitoring up to 40 kHz, 1 pre-select value with relay output and LED indicator, 2-, 3-, 4-wire and NAMUR sensors as well as rotary encoder connectable, Start-up delay, Menu driven operation via 4 front keys, Construction type: modular terminal housing in Makrolon, System KF
For use in the switch cabinet/switch cabinet module, Rated voltage: 200 … 230 V AC ; 100 … 130 V AC; 50/60 Hz
20 VDC … 30 VDC
Pepperl+Fuchs KFU8-DW-1.D Rotation Speed Monitors
KFU8-DWB-1.D
Rotation Speed Monitor
1-channel signal conditioner, Universal usage at different power supplies, Dry contact or NAMUR inputs, Input frequency 1 mHz … 12 kHz, 2 relay contact outputs, Start-up override, Configurable by keypad, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508/IEC 61511, Rated voltage: 20 … 90 V DC / 48 … 253 V AC 50 … 60 Hz
KFA5-DWB-Ex1.D
Rotation Speed Monitor
1-channel isolated barrier, 115 V AC supply, Dry contact or NAMUR inputs, Input frequency 1 mHz … 5 kHz, 2 relay contact outputs, Start-up override, Configurable by keypad, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508/IEC 61511
S1SD-1FI-1R
Rotation Speed Monitor
1-channel signal conditioner, 24 V DC supply, Input for 2- or 3-wire sensors, Input frequency 10 mHz … 50 kHz, Relay contact output, Start-up override and restart inhibit, Configurable by DIP switches and software, Connection via screw terminals

Ordering Models of Pepperl+Fuchs KFU8-DW-1.D Rotation Speed Monitors

Pepperl+Fuchs KFU8-DW-1.D Rotation Speed Monitors
MTL:
MTL3046B,discontinued,replaced by:MTL5541
MTL3042,discontinued,replaced by:MTL5546Y
MTL5053,discontinued,replaced by:MTL5553
MTL5995,discontinued,replaced by:F101-PS
MTL3000 SERIES (200mA)
MTL4041A,discontinued,replaced by:MTL4541A
MTL4041B,discontinued,replaced by:4541B
MTL5042,discontinued,replaced by:MTL5541
MTL5061,discontinued,replaced by:MTL5561
MTL4842,discontinued,replaced by:MTL4852
FP32