Pepperl+Fuchs KCD2-RR2-Ex1 Resistance Repeaters

Product Features of Pepperl+Fuchs KCD2-RR2-Ex1 Resistance Repeaters

Resistance Repeater KCD2-RR2-Ex1

1-channel isolated barrier
24 V DC supply (Power Rail)
Resistance and RTD input (Pt100, Pt500, Pt1000)
Resistance output
Accuracy 0.1 %
Line fault detection (LFD) for Pt100
Housing width 12.5 mm
SIL 2 (SC 3) acc. to IEC/EN 61508
Technical data of Pepperl+Fuchs KCD2-RR2-Ex1 Resistance Repeaters

General specifications of Pepperl+Fuchs KCD2-RR2-Ex1 Resistance Repeaters

Signal type Analog input

Functional safety related parameters of Pepperl+Fuchs KCD2-RR2-Ex1 Resistance Repeaters

Safety Integrity Level (SIL) SIL 2
Systematic capability (SC) SC 3

Supply of Pepperl+Fuchs KCD2-RR2-Ex1 Resistance Repeaters

Connection Power Rail or terminals 9+, 10-
Rated voltage 19 … 30 V DC
Ripple within the supply tolerance
Rated current < 28 mA
Power consumption 0.35 W (24 V and 1 mA sense current), 0.85 W (30 V and 10 mA sense current)

Input of Pepperl+Fuchs KCD2-RR2-Ex1 Resistance Repeaters

Connection side field side
Connection terminals 1, 2, 3, 4
Line fault detection yes , at Pt100
Lead resistance ≤ 10 % of resistance value
Transmission range 0 … 10 mA
Available voltage 7 V
Line fault detection < 30 nA

Output of Pepperl+Fuchs KCD2-RR2-Ex1 Resistance Repeaters

Connection side control side
Connection terminals 5-, 7-, 6+, 8+
Current 0 … 10 mA
Available voltage 0 … 4.2 V
Fault signal field voltage < 150 mV or > 4 V, depending on lead disconnected
Reverse polarity protection for I < 10 mA or U < 20 V
Transfer characteristics of Pepperl+Fuchs KCD2-RR2-Ex1 Resistance Repeaters

Accuracy 0.1 %
Deviation Im ≥ 1 mA: ±0.1 % of Rm or ± 0.1 Ω (the larger value is applicable) 
Im < 1 mA: accuracy reduces in proportion to Im. 
e. g. Im = 0.1 mA: ± 1 % of Rm or 1 Ω (the larger value is applicable).
Influence of ambient temperature Im ≥ 1 mA, Rm ≥ 100 Ω: 0.01 %/K in the range -20 … +70 °C (-4 … 158 °F) 
Im < 1 mA or Rm < 100 Ω: temperature stability reduces in proportion to Im or Rm
Settling time ≤ 5 ms
Rise time/fall time ≤ 2 ms (10 … 90%)
Galvanic isolation
Output/power supply functional insulation, rated insulation voltage 50 V AC

Indicators/settings of Pepperl+Fuchs KCD2-RR2-Ex1 Resistance Repeaters

Display elements LED
Control elements DIP switch
Configuration via DIP switches
Labeling space for labeling at the front

Directive conformity of Pepperl+Fuchs KCD2-RR2-Ex1 Resistance Repeaters

Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)

Conformity of Pepperl+Fuchs KCD2-RR2-Ex1 Resistance Repeaters

Electromagnetic compatibility NE 21:2017 
EN IEC 61326-3-2:2018
Degree of protection IEC 60529:2001
Protection against electrical shock UL 61010-1:2012

Ambient conditions of Pepperl+Fuchs KCD2-RR2-Ex1 Resistance Repeaters

Ambient temperature -40 … 70 °C (-40 … 158 °F)

Mechanical specifications of Pepperl+Fuchs KCD2-RR2-Ex1 Resistance Repeaters

Degree of protection IP20
Connection screw terminals
Mass approx. 100 g
Dimensions 12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001

Data for application in connection with hazardous areas of Pepperl+Fuchs KCD2-RR2-Ex1 Resistance Repeaters

EU-type examination certificate BASEEFA 10 ATEX 0061X
Marking Ex-Hexagon II (1)G [Ex ia Ga] IIC 
Ex-Hexagon II (1)D [Ex ia Da] IIIC 
Ex-Hexagon I (M1) [Ex ia Ma] I
Input [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Voltage 9.5 V
Current 39.22 mA
Power 93 mW
Supply
Maximum safe voltage 250 V (Attention! The rated voltage can be lower.)
Output
Maximum safe voltage 250 V (Attention! The rated voltage can be lower.)
Certificate BASEEFA 10 ATEX 0062X
Marking Ex-Hexagon II 3G Ex ec IIC T4 Gc
Galvanic isolation
Input/Output safe electrical isolation acc. to IEC/EN 60079-11:2007, voltage peak value 375 V
Input/power supply safe electrical isolation acc. to IEC/EN 60079-11:2007, voltage peak value 375 V
Directive conformity
Directive 2014/34/EU EN IEC 60079-0:2018 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012

International approvals of Pepperl+Fuchs KCD2-RR2-Ex1 Resistance Repeaters

FM approval
FM certificate FM 19 CA 0039 X , FM 19 US 0067 X
Control drawing 116-0457 (cFMus)
UL approval E106378
Control drawing 116-0332 (cULus)
IECEx approval
IECEx certificate IECEx BAS 10.0024X 
IECEx BAS 10.0025X
IECEx marking [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I 
Ex ec IIC T4 Gc

General information of Pepperl+Fuchs KCD2-RR2-Ex1 Resistance Repeaters

Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications of Pepperl+Fuchs KCD2-RR2-Ex1 Resistance Repeaters

System Classcode
ECLASS 11.0 27210120
ECLASS 10.0.1 27210120
ECLASS 9.0 27210120
ECLASS 8.0 27210120
ECLASS 5.1 27210120
ETIM 8.0 EC002653
ETIM 7.0 EC002653
ETIM 6.0 EC002653
ETIM 5.0 EC001485
UNSPSC 12.1 32101514

Similar Models of Pepperl+Fuchs KCD2-RR2-Ex1 Resistance Repeaters

KCD2-RR2-Ex1 Resistance Repeater
1-channel isolated barrier, 24 V DC supply (Power Rail), Resistance and RTD input (Pt100, Pt500, Pt1000), Resistance output, Accuracy 0.1 %, Line fault detection (LFD) for Pt100, Housing width 12.5 mm, SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Transfer direction: to the control system, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 … 30 V DC, Field device: resistance thermometer, Signal: Resistance, Line fault detection
KFD0-CS-Ex1.51P Current Driver/Repeater
1-channel isolated barrier, 24 V DC supply (loop powered), Current input/output 0 mA … 40 mA, I/P or transmitter power supply, Accuracy 1 %, Reverse polarity protection, SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, Transfer direction: to the field / to the control system, Reverse polarity protection, Safety Integrity Level (SIL): SIL 2, Rated voltage: loop powered, Signal: 1 x 0 … 40 mA, Device: 1 x fire alarm, Signal: 1 x 0 … 40 mA
KFD0-CS-Ex1.54 Repeater
1-channel isolated barrier, 24 V DC supply (loop powered), SMART fire alarm input, Current input 1 mA … 20 mA, Up to SIL 3 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, Transfer direction: to the control system, HART communication, Safety Integrity Level (SIL): SIL 3, Rated voltage: loop powered, Signal: 1 x 1 … 20 mA, Signal [2]: 1 x HART, Device: 1 x fire alarm, Signal: 1 x 1 … 20 mA
KFD0-CS-Ex2.52 Repeater
2-channel isolated barrier, 24 V DC supply (loop powered), Current input/output 4 mA … 20 mA, Accuracy 0.1 %, Entity parameter Io/Isc = 0 mA, Housing width: 20 mm, Number of channels: 2-channel, Transfer direction: to the control system, Rated voltage: loop powered, Signal: 2 x 4 … 20 mA, Signal: 2 x 4 … 20 mA
KFD0-SCS-Ex1.55 SMART Current Driver/Repeater
1-channel isolated barrier, 24 V DC supply (loop powered), Current input/output 4 mA … 20 mA, HART I/P or transmitter power supply, Low voltage drop, Line fault detection (LFD), Up to SIL 2 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, Transfer direction: to the field / to the control system, HART communication, Safety Integrity Level (SIL): SIL 2, Rated voltage: loop powered, Signal: 1 x 4 … 20 mA, Signal [2]: 1 x HART, Signal: 1 x 4 … 20 mA, Line fault detection
KFD2-VR-Ex1.18 Voltage Repeater
1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input 0 V … 12 V, Voltage output 0 V … 12 V, Housing width: 20 mm, Number of channels: 1-channel, Transfer direction: to the control system, Rated voltage: 20 … 35 V DC, Signal: 1 x 0 … 12 V, Signal: 1 x 0 … 12 V, Cut-off frequency: 1.2 kHz (-3 dB)
KFD2-VR-Ex1.19 Voltage Repeater
1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input -10 V … 10 V, Voltage output -10 V … 10 V, Housing width: 20 mm, Number of channels: 1-channel, Transfer direction: to the control system, Rated voltage: 20 … 35 V DC, Signal: 1 x -10 … 10 V, Signal: 1 x -10 … 10 V, Cut-off frequency: 1.2 kHz (-3 dB)
KFD2-VR2-Ex1.50M Voltage Repeater
1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input 0 mV … ± 50 mV, Voltage output 0 mV … ± 50 mV, Selectable up/downscale sensor breakage detection, Housing width: 20 mm, Number of channels: 1-channel, Transfer direction: to the control system, Rated voltage: 19 … 30 V DC, Signal: 1 x -50 … 50 mV, Signal: 1 x -50 … 50 mV, Cut-off frequency: 350 Hz (-3 dB)
KFD2-VR4-Ex1.26 Voltage Repeater
1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input 0 V … -20 V, Vibration sensor inputs, Voltage/current field supply, Voltage output 0 V … -20 V, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, Transfer direction: to the control system, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 … 30 V DC, Signal: 1 x -20 … 0 V, Signal: 1 x -20 … 0 V, Cut-off frequency: 10 kHz (-0,1 dB) 
20 kHz (-1 dB)
KFD0-CS-Ex1.50P Repeater
1-channel isolated barrier, 24 V DC supply (loop powered), Current input/output 4 mA … 20 mA, transmitter power supply, Accuracy 0.1 %, Reverse polarity protection, SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 1-channel, Transfer direction: to the field / to the control system, Reverse polarity protection, Safety Integrity Level (SIL): SIL 2, Rated voltage: loop powered, Signal: 1 x 4 … 20 mA, Device: 1 x fire alarm, Signal: 1 x 4 … 20 mA
Pepperl+Fuchs KCD2-RR2-Ex1 Resistance Repeaters
KFD0-CS-Ex1.54-Y2 Repeater
1-channel isolated barrier, 24 V DC supply (loop powered), SMART fire alarm input, Current input 1 mA … 20 mA, Housing width: 20 mm, Number of channels: 1-channel, Transfer direction: to the control system, HART communication, Rated voltage: loop powered, Signal: 1 x 1 … 20 mA, Signal [2]: 1 x HART, Device: 1 x fire alarm, Signal: 1 x 1 … 20 mA
KFD0-CS-Ex2.50P Repeater
2-channel isolated barrier, 24 V DC supply (loop powered), Current input/output 4 mA … 20 mA, transmitter power supply, Accuracy 0.1 %, Reverse polarity protection, SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Transfer direction: to the field / to the control system, Reverse polarity protection, Safety Integrity Level (SIL): SIL 2, Rated voltage: loop powered, Signal: 2 x 4 … 20 mA, Device: 2 x fire alarm, Signal: 2 x 4 … 20 mA
KFD0-CS-Ex2.51P Current Driver/Repeater
2-channel isolated barrier, 24 V DC supply (loop powered), Current input/output 0 mA … 40 mA, I/P or transmitter power supply, Accuracy 1 %, Reverse polarity protection, SIL 2 (SC 3) acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Transfer direction: to the field / to the control system, Reverse polarity protection, Safety Integrity Level (SIL): SIL 2, Rated voltage: loop powered, Signal: 2 x 0 … 40 mA, Device: 2 x fire alarm, Signal: 2 x 0 … 40 mA
KFD0-CS-Ex2.54 Repeater
2-channel isolated barrier, 24 V DC supply (loop powered), SMART fire alarm input, Current input 1 mA … 20 mA, Up to SIL 3 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Transfer direction: to the control system, HART communication, Safety Integrity Level (SIL): SIL 3, Rated voltage: loop powered, Signal: 2 x 1 … 20 mA, Signal [2]: 2 x HART, Device: 2 x fire alarm, Signal: 2 x 1 … 20 mA
KCD2-RR2-Ex1.SP Resistance Repeater
1-channel isolated barrier, 24 V DC supply (Power Rail), Resistance and RTD input (Pt100, Pt500, Pt1000), Resistance output, Accuracy 0.1 %, Line fault detection (LFD) for Pt100, Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Transfer direction: to the control system, Safety Integrity Level (SIL): SIL 2, Rated voltage: 19 … 30 V DC, Field device: resistance thermometer
KFD0-CS-Ex1.52 Repeater
1-channel isolated barrier, 24 V DC supply (loop powered), Current input/output 4 mA … 20 mA, Accuracy 0.1 %, Entity parameter Io/Isc = 0 mA, Housing width: 20 mm, Number of channels: 1-channel, Transfer direction: to the control system, Rated voltage: loop powered, Signal: 1 x 4 … 20 mA, Signal: 1 x 4 … 20 mA
KFD2-VR-Ex1.12 Voltage Repeater
1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input 0 V … 9 V, Voltage output 0 V … 9 V, Housing width: 20 mm, Number of channels: 1-channel, Transfer direction: to the control system, Rated voltage: 20 … 35 V DC, Signal: 1 x 0 … 9 V, Signal: 1 x 0 … 9 V, Cut-off frequency: 1.2 kHz (-3 dB)
KFD2-VR-Ex1.19-Y109129 Voltage Repeater
1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input -10 V … 10 V, Transmission frequency up to 50 kHz, Voltage output -10 V … 10 V, Housing width: 20 mm, Number of channels: 1-channel, Transfer direction: to the control system, Rated voltage: 20 … 35 V DC, Signal: 1 x -10 … 10 V, Signal: 1 x -10 … 10 V, Cut-off frequency: 50 kHz (-3 dB)
KFD2-VR2-Ex1.500M Voltage Repeater
1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input 0 mV … ± 500 mV, Voltage output 0 mV … ± 500 mV, Selectable up/downscale sensor breakage detection, Housing width: 20 mm, Number of channels: 1-channel, Transfer direction: to the control system, Rated voltage: 19 … 30 V DC, Signal: 1 x -500 … 500 mV, Signal: 1 x -500 … 500 mV, Cut-off frequency: 350 Hz (-3 dB)
KFD2-FF-Ex2.RS232 RS 232 Repeater
1-channel isolated barrier, 24 V DC supply (Power Rail), RS 232 input/output, Housing width: 20 mm, Number of channels: 1-channel, Transfer direction: to the control system, Rated voltage: 19 … 30 V DC, Interface: RS 232, Interface: RS 232