The Digital Output Modules output 32-channel or 64-channel transistor contact signals.

The ADV551 and ADV561 can be used in dual redundant configuration.

Item Specifications
Model ADV551 ADV557 ADV561
Number of output channels 32  32  64 
Rated applied voltage 24 V DC 24 V DC 24 V DC
Load voltage 24 V DC, 50 mA 24 V DC, 50 mA 24 V DC, 100 mA
External power supply voltage
range
20.4 to 26.4 V DC 20.4 to 26.4 V DC 20.4 to 26.4 V DC
Output ON voltage maximum
value
2 V DC 2 V DC 2 V DC
Leak current maximum value
when output OFF
0.1 mA 0.1 mA 0.1 mA
Output format Current sink Current sink Current sink
Maximum load current (*1) 100 mA/channel, 26.4 V 100 mA/channel, 26.4 V 100 mA/channel, 26.4 V
Withstanding voltage Between output signal and system: 2 kVAC, For 1 minute Between commons: 500 VAC, For 1
minute, common minus (–) side every 16-channel (*2)
Functions
Status output
     Pulse width output

Time-proportioning output

ON/OFF status output function
One-shot pulse width output
function
Time-proportioning ON/OFF
ON/OFF status output function
—

—

ON/OFF status output function
One-shot pulse width output
function
Time-proportioning ON/OFF
Output response time 3 ms or less (for status output)
10 ms or less (for mixed status and pulse outputs)
Pulse width 8 ms to 7200 s
Pulse width resolution 8 ms, but ON/OFF delay of maximum 1 ms is added
Maximum current
consumption
700 mA (5 V DC)
60 mA (external power supply)
550 mA (5 V DC)
60 mA (external power supply)
700 mA (5 V DC)
120 mA (external power supply)
Weight 0.2 kg 0.3 kg 0.3 kg
External connection Pressure clamp terminal,
Dedicated cable (AKB331), MIL
connector cable
Pressure clamp terminal Dedicated cable (AKB337), MIL
connector cable
Item Specifications
Model ADV859 ADV159 ADV559
Number of I/O channels 16-channel input,
16-channel output
32-channel input 32-channel output
Signal isolation Isolated channels Isolated channels Isolated channels
Input signal Contact input: OFF signal 100 kΩ or more
                     ON signal 200 Ω or less
                      Minimum current value when contact is short-
                     circuited: 1.25 mA
Voltage input:  OFF signal 4.5 to 25 V DC
                     ON signal ±1 V DC, 200 Ω or less
–
Input contact rating 5 V DC, 20 mA or more –
Pushbutton input function Not supported Supported –
Input response time 8 ms (for status input) 8 ms (for status input) –
Minimum ON detection time – 20 ms (for pushbutton input) –
Maximum ON/OFF cycle – 25 Hz (for pushbutton input) –
Output signal Transistor contact – Transistor contact
Output contact rating Inductive load, resistive load:
30 V DC, 100 mA (*1)
– Inductive load, resistive load:
30 V DC, 100 mA (*1)
Output response time 16 ms or less – 16 ms or less
Pulse width 8 ms to 7200 s – 8 ms to 7200 s
Pulse width resolution 8 ms, add max. 1ms for ON/OFF
delay time
– 8 ms, add max. 1ms for ON/OFF
delay time
Maximum current
consumption
450 mA (5 V DC) 330 mA (5 V DC) 570 mA (5 V DC)
Weight 0.3 kg 0.4 kg 0.3 kg
External connection Dedicated cable (KS2) Dedicated cable (KS2) Dedicated cable (KS2)
Compatible card ST2 compatible ST3 compatible ST4 compatible
      *1:      Connect a spark killer diode when driving DC relay.
Item Specifications
Model ADV869 ADV169 ADV569
Number of I/O channels 32-channel input,
32-channel output
64-channel input 64-channel output
Signal isolation Common every 16-channel Common every 16-channel Common every 16-channel
Input signal Contact input: OFF signal 100 kΩ or more
                     ON signal 200 Ω or less
                      Minimum current value when contact is short-
                     circuited: 1.25 mA
Voltage input:  OFF signal 4.5 to 25 V DC
                     ON signal ±1 V DC, 200 Ω or less
–
Input contact rating 5 V DC, 20 mA or more
Pushbutton input function Not supported Not supported –
Input response time 8 ms (for status input) 8 ms (for status input) –
Output signal Transistor contact – Transistor contact
Output contact rating Inductive load, resistive load:
30 V DC, 100 mA (*1)
– Inductive load, resistive load:
30 V DC, 100 mA (*1)
Output response time 16 ms or less – 16 ms or less
Pulse width 8 ms to 7200 s – 8 ms to 7200 s
Pulse width resolution 8 ms, add max. 1 ms for ON/
OFF delay time
– 8 ms, add max. 1 ms for ON/
OFF delay time
Maximum current
consumption
800 mA (5 V DC) 800 mA (5 V DC) 800 mA (5 V DC)
Weight 0.3 kg 0.3 kg 0.3 kg
External connection Dedicated cable (KS9) Dedicated cable (KS9) Dedicated cable (KS9)
Compatible card ST5 compatible ST6 compatible ST7 compatible
n MODELS AND SUFFIX CODES
Digital Input Module
Description
Model     ADV151 Digital Input Module (32-channel, 24 V DC, Isolated)
Suffix
Codes
    -P With pushbutton input
    -E With SOE capture (*1)
  5  Without status display; with no explosion protection
  6  With status display; with no explosion protection
  E Without status display; with explosion protection
  F With status display; with explosion protection
0  Basic type
3  With ISA Standard G3 option and temperature (-20 to 70 °C) option
Option
Codes
    /D5A00 With KS Cable Interface Adapter for 32-channel digital [Model: ATD5A-00]
    /B5S00 With Pressure Clamp Terminal Block for Digital Input [Model: ATB5S-00]
    /B5S10 With Pressure Clamp Terminal Block for Digital Input (surge absorber) [Model: ATB5S-10]
    /B5D00 With Dual Pressure Clamp Terminal Block for Digital Input [Model: ATB5D-00]
    /B5D10 With Dual Pressure Clamp Terminal Block for Digital Input (surge absorber) [Model: ATB5D-10]
    /CCC01 With Connector Cover for MIL Cable [Model: ACCC01]
      *1:      Please refer to GS 33K30D10-50E when using it with the Vnet/IP system, and GS 33K30D20-50E when using it with the
               Vnet system.
Description
Model     ADV141 Digital Input Module (16-channel, 100V – 120 VAC, Isolated)
Suffix
Codes
    -P With pushbutton input
  5  Without status display; with no explosion protection
  E Without status display; with explosion protection
0  Basic type
3  With ISA Standard G3 option and temperature (-20 to 70 °C) option
Option
Code
    /C4S50 With Pressure Clamp Terminal Block for Digital [Model : ATC4S-50]
Description
Model     ADV142 Digital Input Module (16-channel, 200 V – 240 VAC, Isolated)
Suffix
Codes
    -P With pushbutton input
  0  General-purpose type
0  Basic type
3  With ISA Standard G3 option and temperature (-20 to 70 °C) option
Option
Code
    /C4S60 With Pressure Clamp Terminal Block for Digital [Model : ATC4S-60]
Description
Model     ADV157 Digital Input Module (32-channel, 24V DC, Pressure Clamp Terminal support only, Isolated)
Suffix
Codes
    -S Standard type
  5  With no explosion protection
  E With explosion protection
0  Basic type
1  With ISA Standard G3 option
Description
Model     ADV161 Digital Input Module (64-channel, 24 V DC, Isolated)
Suffix
Codes
    -P With pushbutton input
  5  Without status display; with no explosion protection
  E Without status display; with explosion protection
0  Basic type
1  With ISA Standard G3 option
All Rights Reserved. Copyright © 2011, Yokogawa Electric Corporation                                                                     GS 33K50F70-50E   Dec. 1, 2013-00
Digital Output Module
Description
Model     ADV551 Digital Output Module (32-channel, 24 V DC, Isolated)
Suffix
Codes
    -P With pulse width output function/time-proportional output function
  5  Without status display; with no explosion protection
  6  With status display; with no explosion protection
  E Without status display; with explosion protection
  F With status display; with explosion protection
0  Basic type
3  With ISA Standard G3 option and temperature (-20 to 70 °C) option
Option
Codes
    /D5A00 With KS Cable Interface Adapter for 32-channel Digital [Model : ATD5A-00]
    /D5S00 With Pressure Clamp Terminal Block for Digital Output [Model : ATD5S-00]
    /D5S10 With Pressure Clamp Terminal Block for Digital Output (surge absorber) [Model : ATD5S-10]
    /D5D00 With Dual Pressure Clamp Terminal Block for Digital Output [Model : ATD5D-00]
    /D5D10 With Dual Pressure Clamp Terminal Block for Digital Output (surge absorber) [Model : ATD5D-10]
    /CCC01 With Connector Cover for MIL Cable [Model : ACCC01]
Description
Model     ADR541 Relay Output Module (16-channel, 24 to 110 V DC/100 to 240 VAC, Isolated)
Suffix
Codes
    -P With pulse width output function/time-proportional output function
  5  Without status display; with no explosion protection
  E Without status display; with explosion protection
0  Basic type
3  With ISA Standard G3 option and temperature (-20 to 70 °C) option
Option
Code
    /C4S70 With Pressure Clamp Terminal Block for Digital Input [Model : ATC4S-70]
Description
Model     ADV557 Digital Output Module (32-channel, 24 V DC, Pressure Clamp Terminal support only, Isolated)
Suffix
Codes
    -S Standard type
  5  With no explosion protection
  E With explosion protection
0  Basic type
1  With ISA Standard G3 option
Description
Model     ADV561 Digital Output Module (64-channel, 24 V DC, Isolated)
Suffix
Codes
    -P With pulse width output function/time-proportional output function
  5  Without status display; with no explosion protection
  E Without status display; with explosion protection
0  Basic type
1  With ISA Standard G3 option
All Rights Reserved. Copyright © 2011, Yokogawa Electric Corporation                                                                     GS 33K50F70-50E    Apr. 1, 2013-00
<<Contents>>  <<Index>>                                                                                                                                            13
Digital I/O Module
Description
Model     ADV859 Digital I/O Module for Compatible ST2 (16-channel input/16-channel output, Isolated channels)
Suffix
Codes
    -P With pulse width function/time-proportional output function
  0  Always 0
0  Basic type
1  With ISA Standard G3 option
Description
Model     ADV159 Digital Input Module for Compatible ST3 (32-channel, Isolated channels)
Suffix
Codes
    -P With pushbutton input
  0  Always 0
0  Basic type
1  With ISA Standard G3 option
Description
Model     ADV559 Digital Output Module for Compatible ST4 (32-channel output, Isolated channels)
Suffix
Codes
    -P With pulse width function/time-proportional output function
  0  Always 0
0  Basic type
1  With ISA Standard G3 option
Description
Model     ADV869 Digital I/O Module for Compatible ST5
(32-channel input/32-channel output, Isolated, Common Minus Side Every 16-channel)
Suffix
Codes
    -P With pulse width function/time-proportional output function
  0  Always 0
0  Basic type
1  With ISA Standard G3 option
Description
Model     ADV169 Digital Input Module for Compatible ST6 (64-channel, Isolated, Common Minus Side Every 16-channel)
Suffix
Codes
    -P Standard type
  0  Always 0
0  Basic type
1  With ISA Standard G3 option
Description
Model     ADV569 Digital Output Module for Compatible ST7
(64-channel output, Isolated, Common Minus Side Every 16-channel)
Suffix
Codes
    -P With pulse width function/time-proportional output function
  0  Always 0
0  Basic type
1  With ISA Standard G3 option
n ORDERING INFORMATION
Specify the model and suffix codes.
For selecting the right products for explosion protection, please refer to TI 33Q01J30-01E without fail.

More Yokogawa Products for your choice:  

We are specialized in intelligent instruments, including : Transmitters, Flowmeters, Analyzers,Communicators, Safety Barriers, Sensors,Gas Detectors, PLC(DCS), Multimeters, Calibrators, Communicators, Recorder, Inverters, Positioners, Valves, Soft Starters, Circuit Breakers, Contactors, Rail Switches, Power Supply, HMI, Terminal Block, Relay etc.