Experion Controller Overview
Honeywell offers multiple ExperionPKS controllers, ranging from embedded controller platforms with dedicated IO hardware
to PC based control environments for supervisory control tasks or simulation. They all support one or more different network
types to integrate the controllers with the ExperionPKS Server. They share a common Control Execution Environment (CEE)
software infrastructure and a common builder tool. Together with the different station types, they form the ExperionPKS
system. This specifications document provides details specifically related to the ExperionPKS C300 controller.
C300 Configuration Options
| C300 Configuration Options | ||||||||||||||||||||||||||||
| 50 ms CEE | 20 ms CEE4 | |||||||||||||||||||||||||||
| Control Networks Supported | FTE only 1 | FTE only 1 | ||||||||||||||||||||||||||
| Supported C300 Models 6, 7 | CC-PCNT01
CC-PCNT02 |
CC-PCNT01
CC-PCNT02 |
||||||||||||||||||||||||||
| Device Index Configuration | Between 1 and 510 | Between 1 and 510 | ||||||||||||||||||||||||||
| IOTA Size | 6 inches | 6 inches | ||||||||||||||||||||||||||
| Number of I/O Links Supported | 2 | 2 | ||||||||||||||||||||||||||
| I/O Link Speeds Available | 375 Kbaud (PMIO Link) 750 Kbaud (Series C IO Link) |
750 Kbaud (Series C IO Link) 375 Kbaud (PMIO Link) is not |
||||||||||||||||||||||||||
| Base Execution Periods Supported | 50 ms | 20 ms (optional)4 | ||||||||||||||||||||||||||
| Redundancy Supported | Yes | Yes | ||||||||||||||||||||||||||
| Remote – Non-Series C I/O Supported | Yes – PM I/O or Series A I/O 3 |
No – Only Series C I/O supported with limited capacities. |
||||||||||||||||||||||||||
| I/O Module Execution Period | 50 ms | 20 ms | ||||||||||||||||||||||||||
| Configurable Values for CM/SCM/RCM Execution Periods 5 | 50, 100, 200, 500, 1000, 2000, 5000, 10000, 20000, 300000, 60000 ms. |
20, 40, 80, 200, 400, 800 ms. CMs Only – SCM/RCM/MR |
||||||||||||||||||||||||||
| Configurable Values of Peer Update Rates (period). Defines the period at which data is updated for all ‘pull/get’ requests for peer data required by all blocks within a CEE. |
100, 200, 500, 1000 ms. | 100, 200, 500, 1000 ms. | ||||||||||||||||||||||||||
| C300 Time Source | SNTP, PTPv2 | SNTP, PTPv2 | ||||||||||||||||||||||||||
| SNTP Update Period | 1 minute | 1 minute | ||||||||||||||||||||||||||
| GPS Time Support2 | No | No | ||||||||||||||||||||||||||
| PTP Update Period | 30 seconds | 30 seconds | ||||||||||||||||||||||||||
| Note 1 – Currently, every C300 must be connected to a Control Firewall Note 2 – A GPS connector is available on the IOTA, but it is not supported until a future release. Note 3 –C300 20ms supports only Series C I/O. Note 4 – Requires separately loaded Firmware Version and License. C300 20 ms CEE may ONLY be used for |
||||||||||||||||||||||||||||
| Note 5- Slower execution periods are supported for Profit Controller Block only Note 6- C300 controller CC-PCNT02 replaces CC-PCNT01 for new installations and field replacements. Note 7- C300 controller must use CC-PCNT02 model with extended functionality firmware image for C300 extended |
||||||||||||||||||||||||||||
CW4500 ,P/N 6560010024
Direct Station (CV-STAD01) – 4 pcs.
DSA SERVER ENABLER, PER CONNECTION (CV-XRESR1) – 1 pcs.
Experion Software Protection Dongle Enabler (EP-DONENB) – 1 pcs.
Experion USB Dongle (EP-DONUSB) – 2 pcs.
MC-TAMR03 51309218-175
MC-TAOY22 80366481-175
MC-TDIY22 51204160-175
MC-TDOY22 80366183-175
MC-TLPA02 51309204-175
We are specialized in intelligent instruments, including : Transmitters, Flowmeters, Analyzers,Communicators, Safety Barriers, Sensors,Gas Detectors, PLC(DCS), Multimeters, Calibrators, Communicators, Recorder, Inverters, Positioners, Valves, Soft Starters, Circuit Breakers, Contactors, Rail Switches, Power Supply, HMI, Terminal Block, Relay etc.