MODEL AND SUFFIX CODES

MODEL AND SUFFIX CODES

Description

Model SAI143 Analog Input Module (4 to 20 mA, 16 channels, module isolation)

Suffix

Codes

-S Standard type

-H With HART communication [Release: R1.02.00] (*1)

5 For pressure clamp terminal block or MIL cable with no explosion protection

6 With signal cable interface adapter and no explosion protection (*2)

E For pressure clamp terminal block or MIL cable with explosion protection

F With signal cable interface adapter and explosion protection (*2)

 3 With ISA Standard G3 and temperature (-20 to 70 ºC)

 C With ISA Standard G3 and high-density installation (-20 to 70 ºC) (*5)

Option

Codes

/A4S00 With pressure clamp terminal block for analog

[Model: STA4S-00]

/A4S10 With pressure clamp terminal block for analog (with surge absorber)

[Model: STA4S-10]

/A4D00 With dual-redundant pressure clamp terminal block for analog (*3)

[Model: STA4D-00]

/A4D10 With dual-redundant pressure clamp terminal block for analog (with surge absorber) (*3)

[Part name: STA4D-10]

/PRP With prevention pin of false insertion (*4)

/CCC01 With connector cover for MIL cable (for flat ribbon cable)

[Model: SCCC01]

Description

STANDARD SPECIFICATIONS

l Current Input Module

This module inputs 4 to 20 mA signals from the field.

The SAI143 can be made dual redundant.

Item Specifications

Model SAI143 (*1)

Number of input channels 16 channels, module isolation (*5)

Rated input range 4 to 20 mA

Permissible input range 0 to 25 mA

Input impedance during Power-ON 250 Ω+ Current value

Voltage drop in the input protection circuit inside the module (*6)

Input impedance during Power-OFF 500 kΩ minimum

Rated accuracy SAI143-S : ±16 µA (Input range 1 to 23 mA)

SAI143-H : ±16 µA (Input range 0.05 to 23 mA) (*3) (*4)

Data update frequency 40 ms

Temperature drift ±16 µA/10 °C

Transmitter power supply

16.15 V minimum (at 20 mA)

26.4 V maximum (at 0 mA)

(Output current limit: 25 mA)

2/4-wire setting Individual channel setting

Changed by setting pins

Withstand voltage 1.5 kV AC between input signal and system for 1 minute (*2)

Maximum current consumption 5 V system: 320 mA,

24 V system: 550 mA

Weight Approx. 0.34 kg (For pressure clamp terminal block or MIL cable)

Approx. 0.39 kg (With signal cable interface adapter)

External connection

Pressure clamp terminal

MIL cable

Dedicated signal cable

Support PRM Available (SAI143-H)

Transmitter power supply ON/OFF

function (*7) Available in 2-wire setting, for all 16 channels at the same time

We are specialized in intelligent instruments, including : Transmitters, Flowmeters, Analyzers,Communicators, Safety Barriers, Sensors,Gas Detectors, PLC(DCS), Multimeters, Calibrators, Communicators, Recorder, Inverters, Positioners, Valves, Soft Starters, Circuit Breakers, Contactors, Rail Switches, Power Supply, HMI, Terminal Block, Relay etc.