Function of Honeywell 8C-TDILA1 Digital Input IOTA Modules

Digital Input Sequence of Events
Function
The Digital Input Sequence of Events (DISOE) accepts 24VDC discrete signals as discrete inputs. The inputs can be time
tagged to support 1ms resolution Sequence of Events
Notable Features
• Three modes of operation:
– Normal (20ms PV scan)
– Sequence of Events (1ms resolution SOE,20ms PV scan)
– Low Latency (5ms PV scan)
• Extensive internal diagnostics for data integrity
• Optional redundancy
• Internal or external field power selection
• On board excitation power (no need for marshalling power)
• Direct / Reverse Input Indication
• Galvanic Isolation
Detail Specifications – Digital Input Sequence of Events

Parameter Specification of Honeywell 8C-TDILA1 Digital Input IOTA Modules

Input / Output Module
8C-PDISA1 – Digital Input Sequence of Events, Coated
8U-PDISA1 – Digital Input Sequence of Events, Uncoated
IOTA Modules
8C-TDILA1 Non Redundant, Coated 9”
8U-TDILA1 Non Redundant, Uncoated 9”
8C-TDILB1 Redundant, Coated. 12”
8U-TDILB1 Redundant, Uncoated 12”
Input Channels 32
Input Channel Scanning (PV) Normal = 20ms ; Fast = 5ms
Digital Input Resolution for Sequence of Events (SOE) 1ms
Voltage Rating 24 VDC
Module current rating 95 mA
Galvanic Isolation (any input terminal voltage
referenced to common) 1000 VAC RMS or ±1000 VDC
Module Removal and Insertion
Under Power Supported
Isolation Technique Optical (in IOM)
DI Power Voltage Range 18 to 30 VDC
ON Sense Voltage/Current 13 VDC (min) or 3 mA (min)
Temperature Operating Temperature 0 to 60 ℃
Storage temperature -40 to 85 ℃
Series 8 Controller and I/O Specification, S803-150-110 18
OFF Sense Voltage/Current 5 VDC (max) or 1.2 mA (max)
Input Impedance 4.2 KΩ
Absolute Delay Across Input Filter and Isolation 5 ms ± 20%
Field Resistance for Guaranteed ON Condition 300 Ωmax @ 15 VDC
Field Resistance for Guaranteed OFF Condition 30 KΩmin @ 30 VDC
Agency certifications Class I, Division 2, Group A, B, C, D; T4 Class I,
Zone 2 AEx/ Ex nA II C T4
 Class I, Division 2, Group A, B, C, D; T4 Class I,
Zone 2, Ex nA II C T4

Honeywell 8C-TDILA1 Digital Input IOTA Modules