Experion Controller Overview

Honeywell offers multiple ExperionPKS controllers, ranging from embedded controller platforms with dedicated IO hardware

to PC based control environments for supervisory control tasks or simulation. They all support one or more different network

types to integrate the controllers with the ExperionPKS Server. They share a common Control Execution Environment (CEE)

software infrastructure and a common builder tool. Together with the different station types, they form the ExperionPKS

system. This specifications document provides details specifically related to the ExperionPKS C300 controller.

C300 Configuration Options

C300 Configuration Options
50 ms CEE 20 ms CEE4
Control Networks Supported FTE only 1 FTE only 1
Supported C300 Models 6, 7 CC-PCNT01

CC-PCNT02

CC-PCNT01

CC-PCNT02

Device Index Configuration Between 1 and 510 Between 1 and 510
IOTA Size 6 inches 6 inches
Number of I/O Links Supported 2  2 
I/O Link Speeds Available 375 Kbaud (PMIO Link)
750 Kbaud (Series C IO
Link)
  750 Kbaud (Series C IO
  Link)

   375 Kbaud (PMIO Link) is not
   supported

Base Execution Periods Supported 50 ms 20 ms (optional)4
Redundancy Supported Yes Yes
Remote – Non-Series C I/O Supported Yes – PM I/O or Series A
I/O 3
No – Only Series C I/O
supported with limited
capacities.
I/O Module Execution Period 50 ms 20 ms
Configurable Values for CM/SCM/RCM Execution Periods 5 50, 100, 200, 500, 1000,
2000, 5000, 10000,
20000, 300000, 60000
ms.
20, 40, 80, 200, 400, 800
ms.

CMs Only – SCM/RCM/MR
not supported

Configurable Values of Peer Update Rates (period).
Defines the period at which data is updated for all ‘pull/get’
requests for peer data required by all blocks within a CEE.
100, 200, 500, 1000 ms. 100, 200, 500, 1000 ms.
C300 Time Source SNTP, PTPv2 SNTP, PTPv2
SNTP Update Period 1 minute 1 minute
GPS Time Support2 No No
PTP Update Period 30 seconds 30 seconds
Note 1 – Currently, every C300 must be connected to a Control Firewall
Note 2 – A GPS connector is available on the IOTA, but it is not supported until a future release.

Note 3 –C300 20ms supports only Series C I/O.

Note 4 – Requires separately loaded Firmware Version and License.  C300 20 ms CEE may ONLY be used for
                Honeywell Turbine Control Solution (TMCS) in R410.1.

Note 5- Slower execution periods are supported for Profit Controller Block only
Note 6- C300 controller CC-PCNT02 replaces CC-PCNT01 for new installations and field replacements.

Note 7-  C300 controller must use CC-PCNT02 model with extended functionality firmware image for C300 extended
                functionalities (EIM, Profit Controller)

CW4500 ,P/N 6560010024

Direct Station (CV-STAD01) – 4 pcs.

DSA SERVER ENABLER, PER CONNECTION (CV-XRESR1) – 1 pcs.

Experion Software Protection Dongle Enabler (EP-DONENB) – 1 pcs.

Experion USB Dongle (EP-DONUSB) – 2 pcs.

MC-TAMR03 51309218-175

MC-TAOY22 80366481-175

MC-TDIY22 51204160-175

MC-TDOY22 80366183-175

MC-TLPA02 51309204-175

We are specialized in intelligent instruments, including : Transmitters, Flowmeters, Analyzers,Communicators, Safety Barriers, Sensors,Gas Detectors, PLC(DCS), Multimeters, Calibrators, Communicators, Recorder, Inverters, Positioners, Valves, Soft Starters, Circuit Breakers, Contactors, Rail Switches, Power Supply, HMI, Terminal Block, Relay etc.