Pepperl+Fuchs KFD2-STC4-Ex1 SMART Transmitter Power Supply
Features
• 1-channel isolated barrier
• 24 V DC supply (Power Rail)
• Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources
• Output 0/4 mA … 20 mA
• Terminals with test points
• Up to SIL 2 acc. to IEC 61508
Overview of Pepperl+Fuchs KFD2-STC4-Ex1 SMART Transmitter Power Supply
Manufacturer : Pepperl+Fuchs
Product No : KFD2-STC4-EX1
Product type : SMART Transmitter Power Supply
This product is a replacement for KFD2-CR-EX1.30
1-channel isolated barrier
24 V DC supply (Power Rail)
Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources
Output 4 mA … 20 mA
Terminals with test points
Up to SIL2 acc. to IEC 61508
Input : 3-wire transmitter
Rated voltage : 20 … 35 V DC
SIL/IEC 61508
Output signal : 0/4 … 20 mA (overload > 25 mA)
Dimensions : 2.0 x 12.4 x 11.5 cm, housing type B2
Function of Pepperl+Fuchs KFD2-STC4-Ex1 SMART Transmitter Power Supply
• This isolated barrier is used for intrinsic safety applications.
• The device supplies 2-wire and 3-wire SMART transmitters in a hazardous area, and can also be used with 2-wire SMART current sources.
• It transfers the analog input signal to the safe area as an isolated current value.
• Digital signals may be superimposed on the input signal in the hazardous or safe area and are transferred bi-directionally.
• If the HART communication resistance in the loop is too low,the internal resistance of 250 Ω between terminals 8 and 9 can be used.
• Test sockets for the connection of HART communicators are integrated into the terminals of the device.
Application of Pepperl+Fuchs KFD2-STC4-Ex1 SMART Transmitter Power Supply
The device supports the following SMART protocols:
• HART
• BRAIN
• Foxboro
General specifications of Pepperl+Fuchs KFD2-STC4-Ex1 SMART Transmitter Power Supply
Signal type Analog input
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Supply of Pepperl+Fuchs KFD2-STC4-Ex1 SMART Transmitter Power Supply
Connection Power Rail or terminals 14+, 15-
Rated voltage 20 … 35 V DC
Ripple within the supply tolerance
Power dissipation 1.4 W
Power consumption 1.8 W
We are specialized in intelligent instruments, including : control system, transmitters, flow meters,sensors, recorders, analyzers, control valves, controllers, PLC’s, etc.