Product Features of MTL SD275X Surge Protection Devices SPD
MTL SD range 
Ultra-slim user-friendly devices for protecting electronic equipment and systems against surges on signal and I/O cabling
• Range of ATEX Certified intrinsically safe surge protectors
• Ultra-slim space-saving design;easy installation
• Multistage hybrid protection circuitry – 20kA maximum surge current
• Range of voltage ratings – to suit all process I/O applications
• High bandwidth, low resistance, RTD, PSTN and 3-wire transmitter versions available

• 10 year product warranty

Product Overview of MTL SD275X Surge Protection Devices SPD

The SD range is a series of surge protection devices combine unparalleled packing densities, application versatility, proven reliable hybrid circuitry, simple installation and optional ‘loop disconnect’ facilities – features which make the range the ultimate surge protection solution for process equipment, I/O systems and communications networks.
The exceptionally high packing densities are the consequence of an ultra slim ‘footprint’ for individual modules which can thus‘double-up’ as feedback terminals. Each module provides full hybrid surge protection for 2 and 3 wire loop protection.

MTL SD275X Surge Protection Devices SPD

Modules with a comprehensive range of voltage ratings cover all process related signals such as RTDs, THCs, 4 to 20mA loops, telemetry outstations, shut-down systems and fire and gas detectors.

Optional ‘loop disconnect’, is a feature which allows commissioning and maintenance to be carried out without removal of the surge protection device. This facility is provided by the SD07, SD16, SD32 and SD55 units. In addition, a third connection on the field and safe side of the protector is provided in order to terminate screens safely

MTL SD275X Surge Protection Devices SPD

For three wire applications the specially designed SDRTD (Resistance Temperature Detector) and the SD32T3, (for separately powered 4-20mA loops) provide full 3-wire protection in a single compact unit. The recommended choice for the protection of 3-wire pressure transducers on low power circuits is the SD07R3.
MTL SD275X Surge Protection Devices SPD

For higher bandwidth applications, the SDR range has been developed to meet the demands of today’s highest speed communication systems.
120V and 240V AC versions are available for I/O and power supplies up to three Amps of load current and telephone networks can be protected by the SDPSTN.

One simple manual operation clamps modules securely onto DIN rail, which automatically provides the essential high-integrity earth connection.

‘Top-hat’ (T-section) DIN rail is generally suitable for mounting SD modules although for adverse environments, a specially-plated version is available. A comprehensive range of mounting and earthing accessories can also be supplied. 

Analogue inputs (high-level)
2-wire transmitters, 4-20mA, conventional and smart

The SPDs recommended for use with‘conventional’ and ‘smart’ 4-20mA transmitters (fed by a well-regulated supply) are the SD32 and SD55, the choice depending upon the maximum working voltage of the system (32V and 55V respectively). The diagram illustrates a prime example of an application for which the fuse/disconnect facility is particularly useful, however, both models are available in ‘X’ versions without the optional fuse/disconnect feature.

MTL SD275X Surge Protection Devices SPD

Analogue inputs (low-level)
RTDs
These applications are best served using the SDRTD. For optimum accuracy, the energising current should be chosen to ensure the voltage across the RTD does not exceed 1V over the full measurement range. When using a PT100 device, we recommend an energising current of 1mA.

MTL SD275X Surge Protection Devices SPD

Photocells, THCs, mV sources and turbine flowmeters

The SD07 or SD16 (depending upon the operational voltage) are the favoured choices for this application. SD07X and SD16X are also suitable.

MTL SD275X Surge Protection Devices SPD

Analogue outputs
Controller outputs (I/P converters)

For this application, the recommendations are the SD16, SD32 and SD55 (and the equivalent‘X’ versions), the final choice depending upon the operating voltage.

MTL SD275X Surge Protection Devices SPD

Digital (on/off) inputs
Switches
Suitable SPDs for switches include the SD07, SD16, SD32 and SD55 modules – the choice depending upon the operating voltage of the system. The ‘X’ versions of these are also suitable.
MTL SD275X Surge Protection Devices SPD

Digital (on/off) outputsAlarms, LEDs, solenoid valves, etc
Alarms, LEDs, solenoid valves, etc
The recommended choice for this application is the SD32 or SD32X.
MTL SD275X Surge Protection Devices SPD

Telemetry (PSTN)
Telemetry outstations
The SDPSTN has been designed specifically for the protection of signals transmitted on public switched telephone networks.
MTL SD275X Surge Protection Devices SPD

AC supplied equipment
PLC, I/O systems
For systems on 110-120V ac, the SD150X is the recommended choice and for 220-240V ac systems, the SD275X is recommended.

Technical Data of MTL SD275X Surge Protection Devices SPD

All figures typical at 77°F (25°C) unless
otherwise stated
Protection
Full hybrid line to line
Each line to screen/ground
Max discharge surge current (Imax) (8/20µs)
20kA (8/20µs)
Response time  <1ns
RTD resistance range (SDRTD) 10 to 1500

MTL SD275X Surge Protection Devices SPD

Degradation accuracy (SDRTD at 1mA)
0.1% (RTD resistance > 100 )
0.1W (RTD resistance < 100 )
Ambient temperature
–40°C to +80°C / -40°F to 176°F storage
–40°C to +80°C / -40°F to 176°F working

For IS working applications:
Pi = 1.0W (–30°C to +75°C / -22°F to 167°F)
Pi = 1.2W (–30°C to +60°C / -22°F to 140°F)
Pi = 1.3W (–30°C to +40°C / -22°F to 104°F)

Humidity  5 to 95% RH (non-condensing)
Category tested A2, B2, C1, C2, C3
Overstressed fault mode in=3kA
12kA
9kA (SD150X and SD275X only)
Impulse durability (8/20µs)
10kA
6.5kA (SD150X and SD275X only)

Terminals  2.5mm2(12 AWG)
Mounting  T-section DIN-rail 35 x 7.5 or 35 x 15mm rail(1.38” x 0.3” x 0.6”)
MTL SD275X Surge Protection Devices SPD

Weight 70g approximately (2.5oz)
Case flammability  UL94 V-2

AC durability   1Arms, 5T

MTL SD275X Surge Protection Devices SPD

Service conditions
80kPa – 160kPa
5% – 95% RH
EMC compliance
To Generic Immunity Standards,
EN 61326-1, part 2 for industrial
environments
R&TTE compliance
EN 61326-1, EN 41003 : 1999
EN 60950 – 1 : 2006
(not applicable to SD150X and SD275X)
LVD compliance
SD150X & SD275X
EN 60950 – 1 : 2006, EN 61010 : 2010
SDPST
EN 41003 : 1999
IEC compliance
EN 61643-21:2001
ANSI/IEEE testing
C62.41-1-2002
C62.41-2-2002

C62.45-2002

Ordering Models of MTL SD275X Surge Protection Devices SPD

Ordering Codes of MTL SD275X Surge Protection Devices SPD

Part Number & Description of MTL SD275X Surge Protection Devices SPD

Digital Input    MTL SD275X Surge Protection Devices SPD

MTL4501-SR     1ch DI failsafe solid-state output + LFD alarm        
MTL4504          1ch DI relay output + LFD alarm + phase reversal
MTL4510          4ch DI solid-state output        
MTL4510B        4ch DI multifunction solid-state output
MTL4511          1ch DI relay output
MTL4513          2ch DI solid-state output        
MTL4514/B       1ch DI relay output + LFD alarm     
MTL4516          2ch DI relay output
MTL4516C        2ch DI with changeover relay output     

MTL4517          2ch DI relay output + LFD alarm  

Digital Output  MTL SD275X Surge Protection Devices SPD

MTL4521          Loop powered solenoid driver
MTL4521L         Loop powered solenoid driver IIC    
MTL4523          Solenoid driver with LFD
MTL4523L         Loop powered solenoid driver + LFD       
MTL4523R         Solenoid driver with LFD
MTL4523V/VL    Solenoid/Alarm driver with voltage control    
MTL4524           Switch operated solenoid driver     
MTL4524S         Switch operated solenoid driver, 24V override       
MTL4525           Switch operated solenoid driver low power   

MTL4526           2ch switch operated relay      

Analogue Input   MTL SD275X Surge Protection Devices SPD

MTL4541           1ch 2/3 wire Transmitter repeater
MTL4541A         1ch Transmitter repeater, passive input         
MTL4541AS       1ch Transmitter repeater, passive input, current sink   
MTL4544D          2/3 wire transmitter repeater, dual output   

MTL4544S          2ch 2/3 transmitter repeater, current sink    

Analogue Output  MTL SD275X Surge Protection Devices SPD

MTL4546            1ch 4-20mA smart isolating driver + LFD        
MTL4546C          1ch 4-20mA smart isolating driver + oc LFD   
MTL4546Y          1ch 4-20mA smart isolating driver + oc LFD   
MTL4549            2ch 4-20mA smart isolating driver + LFD        
MTL4549C          2ch 4-20mA smart isolating driver + oc LFD   

MTL4549Y          2ch 4-20mA smart isolating driver + oc LFD   

Temperature Input   MTL SD275X Surge Protection Devices SPD

MTL4575            1ch Temperature converter with alarm
MTL4576-RTD     2ch Temperature converter, RTD   
MTL4576-THC     2ch Temperature converter, THC   

MTL4581            1ch mV/THC isolator for low-level signals  

Pulse and Vibration   MTL SD275X Surge Protection Devices SPD

MTL4531            1ch vibration probe interface
MTL4532            1ch pulse isolator, digital or analogue output         

MTL4533            2ch vibration probe interface

Fire and Smoke   MTL SD275X Surge Protection Devices SPD

MTL4561            2ch loop-powered, for fire and smoke detectors  

General              MTL SD275X Surge Protection Devices SPD

MTL4599             Dummy isolator      

MTL4599N           General purpose feed-through module

MTL4500 Series Barriers     MTL SD275X Surge Protection Devices SPD

MTL SD275X Surge Protection Devices SPD

ICC     MTL SD275X Surge Protection Devices SPD

MTL SD275X Surge Protection Devices SPD

MTL SD275X Surge Protection Devices SPD

MTL SD275X Surge Protection Devices SPD

MTL SD275X Surge Protection Devices SPD

MTL SD275X Surge Protection Devices SPD

MTL SD275X Surge Protection Devices SPD

MTL SD275X Surge Protection Devices SPD

MTL SD275X Surge Protection Devices SPD

We are specialized in intelligent instruments, including : Transmitters, Flowmeters, Analyzers,Communicators, Safety Barriers, Sensors,Gas Detectors, PLC(DCS), Multimeters, Calibrators, Communicators, Recorder, Inverters, Positioners, Valves, Soft Starters, Circuit Breakers, Contactors, Rail Switches, Power Supply, HMI, Terminal Block, Relay etc.