Overview of MTL7707+ MTL7787+ Shunt Diode Safety Barrier
MTL 7700 Intrinsically Safe Barrier
DIN-rail zener barriers limit the amount of energy transferred across the barrier to a level that cannot ignite flammable atmospheres
Description of MTL7707+ MTL7787+ Shunt Diode Safety Barrier
The MTL7700 Intrinsically Safe Barriers are 1- or 2-channel DIN-rail mounted shunt-diode safety barriers that use intrinsically safe explosion-protection techniques to pass electrical signals between safe and hazardous areas, while limiting transferred energy to a level that cannot ignite flammable atmospheres. Connected in series with wiring entering any hazardous area on process plant, MTL7700 Series barriers prevent explosions in all normally occurring explosive atmospheres – including mixtures of air with flammable gases, vapors, dusts and fibers – if a fault or faults develop in the safe area.
MTL7707+ MTL7787+ Shunt Diode Safety Barrier
The MTL7700 is a DIN rail mounting barrier providing quick and easy installation without the need for special hardware. Removable terminals are used for ease of installation, maintenance and for providing a loop disconnect by simply unplugging the terminals from the side of the module. Wire entry is also angled to assist wiring within limited space enclosures. MTL7700 barriers clamp simply and securely onto standard T-section DIN rail, simultaneously making a reliable IS earth connection. For applications where field power is required for switch inputs or 2-wire transmitters, the MTL7700 range provides a bussed power feed facility. When used in conjunction with the MTL7798 power feed module the user has a fully protected, electronically fused supply to many barriers with no additional wiring required.
MTL7707+ MTL7787+ Shunt Diode Safety Barrier
All MTL7700 Series barriers are based on the same simple principle. Each channel contains two stages of pulse-tested Zener or forward connected diodes and an ‘infallible’ terminating resistor. In the event of an electrical fault in the safe area, the diodes limit the voltage that can reach the hazardous area and the resistor limits the current. A fuse protects the diodes, and the two stages of voltage limitation ensure continued safety if either stage should fail. No active output current limiting circuits are employed. All models (except MTL7707P+ and MTL7729P+, ‘ia’ ‘IIB’) are certified ‘ia’ for all zones and ‘IIC’ for all explosive atmospheres.
Features
* Removable terminals for easy cabling
* Bussed power feed to other modules
* Relay and solid state switch modules
* Dual channel variants: 6.3mm per channel
* Barrier protection module
* Proximity detector inputs
* Electronic fusing
* Direct replacement for MTL700 Series barriers
* Compatible terminal numbering and safety descriptions
Application of MTL7707+ MTL7787+ Shunt Diode Safety Barrier
Here’s how some of our customers use this product…
Protecting Sensor Circuits in a Hazardous Location
The Background: Our customer is a ceramics manufacturer seeking a means to protect sensor circuits in a hazardous area location.
The Problem: The customer utilizes methanol during the annealing process. As a highly flammable substance, the storage area for the methanol is classified as a hazardous area. As such, they must have intrinsically safe barriers for all sensor circuits that pass into the methanol storage area.
The Solution: We recommended MTL7700 Intrinsically Safe Barriers. The 7700 is a shunt-diode barrier that limits the amount of energy allowed to pass between safe and hazardous areas to a level that cannot ignite flammable atmospheres. They are DIN-rail mounted which provides quick and easy installation without the need for special hardware.
MTL7700 series
Product Description
MTL7706+ Shunt-Diode Safety Barrier
MTL7707+ Shunt-Diode Safety Barrier
MTL7707P+ Shunt-Diode Safety Barrier
MTL7710+ Shunt-Diode Safety Barrier
MTL7715+ Shunt-Diode Safety Barrier
MTL7715P+ Shunt-Diode Safety Barrier
MTL7722+ Shunt-Diode Safety Barrier
MTL7728+ Shunt-Diode Safety Barrier
MTL7728- Shunt-Diode Safety Barrier
MTL7728ac Shunt-Diode Safety Barrier
MTL7728P+ Shunt-Diode Safety Barrier
MTL7729P+ Shunt-Diode Safety Barrier
MTL7741 Shunt-Diode Safety Barrier
MTL7742 Shunt-Diode Safety Barrier
MTL7743 Shunt-Diode Safety Barrier
MTL7744 Shunt-Diode Safety Barrier
MTL7745 Shunt-Diode Safety Barrier
MTL7755ac Shunt-Diode Safety Barrier
MTL7756ac Shunt-Diode Safety Barrier
MTL7758+ Shunt-Diode Safety Barrier
MTL7758- Shunt-Diode Safety Barrier
MTL7760ac Shunt-Diode Safety Barrier
MTL7761ac Shunt-Diode Safety Barrier
MTL7761Pac Shunt-Diode Safety Barrier
MTL7764+ Shunt-Diode Safety Barrier
MTL7764ac Shunt-Diode Safety Barrier
MTL7765ac Shunt-Diode Safety Barrier
MTL7766ac Shunt-Diode Safety Barrier
MTL7766Pac Shunt-Diode Safety Barrier
MTL7767+ Shunt-Diode Safety Barrier
MTL7778ac Shunt-Diode Safety Barrier
MTL7779+ Shunt-Diode Safety Barrier
MTL7787+ Shunt-Diode Safety Barrier
MTL7787P+ Shunt-Diode Safety Barrier
MTL7788+ Shunt-Diode Safety Barrier
MTL7788R+ Shunt-Diode Safety Barrier
MTL7789+ Shunt-Diode Safety Barrier
MTL7796+ Shunt-Diode Safety Barrier
MTL7796– Shunt-Diode Safety Barrier
MTL7798 Power Feed Module
MTL7799 Dummy Barrier
Stock of MTL7700 ranges: MTL7707+ MTL7787+ Shunt Diode Safety Barrier
MTL7707+ MTL7787+ Shunt Diode Safety Barrier
MTL7707+ MTL7787+ Shunt Diode Safety Barrier
MTL7707+ MTL7787+ Shunt Diode Safety Barrier
MTL7707+ MTL7787+ Shunt Diode Safety Barrier
ICC MTL7707+ MTL7787+ Shunt Diode Safety Barrier
MTL7707+ MTL7787+ Shunt Diode Safety Barrier
MTL7707+ MTL7787+ Shunt Diode Safety Barrier
MTL7707+ MTL7787+ Shunt Diode Safety Barrier
MTL7707+ MTL7787+ Shunt Diode Safety Barrier
MTL7707+ MTL7787+ Shunt Diode Safety Barrier
MTL7707+ MTL7787+ Shunt Diode Safety Barrier
MTL7707+ MTL7787+ Shunt Diode Safety Barrier
MTL7707+ MTL7787+ Shunt Diode Safety Barrier