Product Features of Pepperl+Fuchs KFD0-CC-1 Current Voltage Converters
– Current/Voltage Converter KFD0-CC-1
– 1-channel signal conditioner
– 24 V DC supply (loop powered)
– Current or voltage input
– Output: 4 … 20 mA
– Potentiometer or DIP switch selectable ranges
– Line fault detection (LFD)
Technical Information of Pepperl+Fuchs KFD0-CC-1 Current Voltage Converter KFD0-CC-1 Safety Barriers
General specifications of Pepperl+Fuchs KFD0-CC-1 Current Voltage Converters
Signal type Analog input
Supply
Rated voltage 12 … 35 V DC loop powered
Power dissipation 0.4 W
Input of Pepperl+Fuchs KFD0-CC-1 Current Voltage Converters
Connection side field side
Connection terminals 1+, 2-
Current range 0 … 20 mA , load ≤ 50 Ω
Voltage range 0 … 10 V , load ≥ 100 kΩ
Output of Pepperl+Fuchs KFD0-CC-1 Current Voltage Converters
Connection side control side
Connection terminals 9+, 8-
Load (U -12 V) / 0.02 A
Current output 4 … 20 mA , limited to ≤ 35 mA
Fault signal downscaling ≤ 3 mA
Transfer characteristics of Pepperl+Fuchs KFD0-CC-1 Current Voltage Converters
Deviation
After calibration 0.1 % of full-scale value
Temperature effect span: 0.050 % of span /K ; zero point: 0.060 % of span /K
Linearization ≤ 0.04 % of full-scale value
Influence of supply voltage 6.5 ppm/V
Rise time 250 ms
Galvanic isolation of Pepperl+Fuchs KFD0-CC-1 Current Voltage Converters
Input/Output safe isolation according to EN 50178, rated insulation voltage 253 Veff
Indicators/settings of Pepperl+Fuchs KFD0-CC-1 Current Voltage Converters
Control elements DIP-switch
potentiometer
Configuration via DIP switches
via potentiometer
Labeling space for labeling at the front
Directive conformity of Pepperl+Fuchs KFD0-CC-1 Current Voltage Converters
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Conformity of Pepperl+Fuchs KFD0-CC-1 Current Voltage Converters
Insulation coordination EN 50178
Galvanic isolation EN 50178
Degree of protection IEC 60529
Ambient conditions of Pepperl+Fuchs KFD0-CC-1 Current Voltage Converters
Ambient temperature -20 … 70 °C (-4 … 158 °F)
Mechanical specifications of Pepperl+Fuchs KFD0-CC-1 Current Voltage Converters
Degree of protection IP20
Connection screw terminals
Mass approx. 100 g
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Ordering Codes of Pepperl+Fuchs KFD0-CC-1 Current Voltage Converters
Ordering Models of Pepperl+Fuchs KFD0-CC-1 Current Voltage Converters
KFA6-STR-1.24.500
Power Supply
115/230 V AC supply, Output 24 V DC, 500 mA, Electronic short circuit protection, Power Rail connection
KFD0-SCS-Ex1.55
SMART Current Driver/Repeater
1-channel isolated barrier, 24 V DC supply (loop powered), Current input/output 4 mA … 20 mA, HART I/P or transmitter power supply, Low voltage drop, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508, Rated voltage: loop powered, Explosion protection: Ex protection, Transfer direction: to the field / to the control system
KFD2-CRG2-1.D
Transmitter Power Supply
1-channel signal conditioner, 24 V DC supply (Power Rail), Input 2-wire and 3-wire transmitters and 2-wire current sources, Output 0/4 mA … 20 mA, 2 relay contact outputs, Adjustable energized/de-energized delay, Programmable high/low alarm, Linearization function (max 20 points), Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508/IEC 61511
KFD2-CRG2-Ex1.D
Transmitter Power Supply
1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire transmitters and 2-wire current sources, Output 0/4 mA … 20 mA, 2 relay contact outputs, Adjustable energized/de-energized delay, Programmable high/low alarm, Linearization function (max 20 points), Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508/IEC 61511
KFD2-HLC-Ex1.D
HART Loop Converter
1-channel isolated barrier, 24 V DC supply (Power Rail), HART field device input with transmitter power supply, Usable as signal splitter (1 input and several outputs), 3 analog outputs 4 mA … 20 mA, Sink and source mode output, Configurable by keypad
KFD2-HLC-Ex1.D.2W
HART Loop Converter
1-channel isolated barrier, 24 V DC supply (Power Rail), HART field device input with transmitter power supply, Usable as signal splitter (1 input and several outputs), 2 relay contact outputs (change-over contacts), 3 analog outputs 4 mA … 20 mA, Sink and source mode output, Configurable by keypad
KFD2-STC5-1
SMART Transmitter Power Supply
1-channel signal conditioner, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/4 mA … 20 mA current sink/current source, Terminals with test points, Up to SIL 2 acc. to IEC 61508
KFD2-STC5-1.2O
SMART Transmitter Power Supply
1-channel signal conditioner, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA … 20 mA, current sink/current source, Terminals with test points, Up to SIL 3 acc. to IEC 61508
KFD2-STC5-2
SMART Transmitter Power Supply
2-channel signal conditioner, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/4 mA … 20 mA current sink/current source, Terminals with test points, Up to SIL 2 acc. to IEC 61508
KFD2-STC5-Ex1.2O
SMART Transmitter Power Supply
1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA … 20 mA, current sink/current source, Terminals with test points, Up to SIL 3 acc. to IEC 61508
KFD2-STC5-Ex1.H
SMART Transmitter Power Supply
1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/4 mA … 20 mA current sink/current source, Terminals with test points, High field voltage 17 V DC, Up to SIL 2 acc. to IEC 61508
KFD2-STC5-Ex2
SMART Transmitter Power Supply
2-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/4 mA … 20 mA current sink/current source, Terminals with test points, Up to SIL 2 acc. to IEC 61508
KFU8-CRG2-1.D
Transmitter Power Supply
1-channel signal conditioner, Universal usage at different power supplies, Input 2-wire and 3-wire transmitters and 2-wire current sources, Output 0/4 mA … 20 mA, 2 relay contact outputs, Adjustable energized/de-energized delay, Programmable high/low alarm, Linearization function (max 20 points), Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508/IEC 61511
KFU8-CRG2-Ex1.D
Transmitter Power Supply
1-channel isolated barrier, Universal usage at different power supplies, Input 2-wire and 3-wire transmitters and 2-wire current sources, Output 0/4 mA … 20 mA, 2 relay contact outputs, Adjustable energized/de-energized delay, Programmable high/low alarm, Linearization function (max 20 points), Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508/IEC 61511
KFU8-VCR-1
Transmitter Power Supply/Converter
1-channel signal conditioner, Universal usage at different power supplies, Input 2-wire and 3-wire transmitters, current and voltage sources, Current and voltage output, Rated voltage: 19 … 90 V DC / 48 … 253 V AC
KLD2-FBPS-1.25.360
Fieldbus Power Supply
Output: 25 … 27 V/360 mA, For most fieldbus applications, High-power trunk for high device count and long cable lengths, Installation in Zone 2/Class I, Div. 2, For FOUNDATION Fieldbus H1
KFD2-STC5-Ex1
SMART Transmitter Power Supply
1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/4 mA … 20 mA current sink/current source, Terminals with test points, Up to SIL 2 acc. to IEC 61508
KCD2-STC-1.2O
SMART Transmitter Power Supply
1-channel signal conditioner, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA … 20 mA or 0/1 V … 5 V, Terminal blocks with test sockets, Up to SIL 2 acc. to IEC 61508
KCD2-STC-Ex1
SMART Transmitter Power Supply
1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA … 20 mA or 1 V … 5 V, Housing width 12.5 mm, Up to SIL 2 acc. to IEC 61508
KCD2-STC-Ex1.2O
SMART Transmitter Power Supply
1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA … 20 mA or 0/1 V … 5 V, Terminal blocks with test sockets, Up to SIL 2 acc. to IEC 61508
KCD2-STC-Ex1.ES
SMART Transmitter Power Supply
1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA … 20 mA or 1 V … 5 V, Sink or source mode, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 3 acc. to IEC 61508
KCD2-STC-Ex1.SP
SMART Transmitter Power Supply
1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA … 20 mA or 1 V … 5 V, Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC 61508
KFA6-STR-1.24.4
Power Supply
115/230 V AC supply, Output 24 V DC, 4 A, Fused output, Power Rail connection
KFD0-CS-1.50
Repeater
1-channel signal conditioner, 24 V DC supply (loop powered), Current input/output 4 mA … 20 mA, transmitter power supply, Accuracy 0.1 %, Reverse polarity protection, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system
KFD0-CS-2.50
Repeater
2-channel signal conditioner, 24 V DC supply (loop powered), Current input/output 4 mA … 20 mA, transmitter power supply, Accuracy 0.1 %, Reverse polarity protection, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system
KFD0-CS-Ex1.50P
Repeater
1-channel isolated barrier, 24 V DC supply (loop powered), Current input/output 4 mA … 20 mA, transmitter power supply, Accuracy 0.1 %, Reverse polarity protection, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system
KFD0-CS-Ex1.51P
Current Driver/Repeater
1-channel isolated barrier, 24 V DC supply (loop powered), Current input/output 0 mA … 40 mA, I/P or transmitter power supply, Accuracy 1 %, Reverse polarity protection, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system
KFD0-CS-Ex2.50P
Repeater
2-channel isolated barrier, 24 V DC supply (loop powered), Current input/output 4 mA … 20 mA, transmitter power supply, Accuracy 0.1 %, Reverse polarity protection, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system
KFD0-CS-Ex2.51P
Current Driver/Repeater
2-channel isolated barrier, 24 V DC supply (loop powered), Current input/output 0 mA … 40 mA, I/P or transmitter power supply, Accuracy 1 %, Reverse polarity protection, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system
KFD2-STC3-Ex1
SMART Transmitter Power Supply
1-channel isolated barrier, 24 V DC supply (Power Rail), 2-wire SMART transmitter, Output 4 mA … 20 mA, SMART capable up to 40 kHz (-1dB), Suitable for Honeywell DE protocol, Terminals with test points
KFD2-STC4-Ex2-Y1
SMART Transmitter Power Supply, Output Current Sink
2-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire SMART transmitters, Output 0/4 mA … 20 mA current sink, Terminal blocks with test sockets, Up to SIL 2 acc. to IEC 61508
KFD2-STC5-Ex1
SMART Transmitter Power Supply
1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/4 mA … 20 mA current sink/current source, Terminals with test points, Up to SIL 2 acc. to IEC 61508
KFD2-STC5-Ex1.2O.H
SMART Transmitter Power Supply
1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA … 20 mA, current sink/current source, Terminals with test points, High field voltage 17 V DC, Up to SIL 3 acc. to IEC 61508
KCD2-STC-Ex1.2O.DE
SMART Transmitter Power Supply
1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA … 20 mA or 0/1 V … 5 V, Terminal blocks with test sockets, Up to SIL 2 acc. to IEC 61508
KCD2-STC-Ex1.2O.ES
SMART Transmitter Power Supply
1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA … 20 mA or 0/1 V … 5 V, Terminal blocks with test sockets, Up to SIL 3 acc. to IEC 61508
KCD2-STC-Ex1.ES.SP
SMART Transmitter Power Supply
1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA … 20 mA or 1 V … 5 V, Sink or source mode, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 3 acc. to IEC 61508
KFD0-CS-2.51P
Current Driver/Repeater
2-channel signal conditioner, 24 V DC supply (loop powered), Current input/output 0 mA … 40 mA, I/P or transmitter power supply, Accuracy 1 %, Reverse polarity protection, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system
KFD0-SCS-1.55
SMART Current Driver/Repeater
1-channel signal conditioner, 24 V DC supply (loop powered), Current input/output 4 mA … 20 mA, HART I/P or transmitter power supply, Low voltage drop, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system
KFD2-HLC-Ex1.D.4S
HART Loop Converter
1-channel isolated barrier, 24 V DC supply (Power Rail), HART field device input with transmitter power supply, Usable as signal splitter (1 input and several outputs), 4 relay contact outputs (NO contact), 3 analog outputs 4 mA … 20 mA, Sink and source mode output, Configurable by keypad
KFD2-STC4-Ex1.2O-Y1
SMART Transmitter Power Supply, Output Current Sink
1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA … 20 mA, current sink, Terminal blocks with test sockets, Up to SIL 3 acc. to IEC 61508
KFD2-STV4-Ex1-2
SMART Transmitter Power Supply
1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/2 V … 10 V, Terminals with test points, Up to SIL 2 acc. to IEC 61508
KFD2-STV4-Ex1.2O-1
SMART Transmitter Power Supply
1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Signal splitter (1 input and 2 outputs), Dual output 0/1 V … 5 V, Terminal blocks with test sockets, Up to SIL 3 acc. to IEC 61508
KFD2-STV4-Ex2-1
SMART Transmitter Power Supply
2-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire SMART transmitters, Output 0/1 V … 5 V, Terminals with test points, Up to SIL 2 acc. to IEC 61508
KFD2-STV4-Ex2-2
SMART Transmitter Power Supply
2-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire SMART transmitters, Output 0/2 V … 10 V, Terminals with test points, Up to SIL 2 acc. to IEC 61508
KFD2-STV5-Ex1-1
SMART Transmitter Power Supply
1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/1 V … 5 V, Terminals with test points, Up to SIL 2 acc. to IEC 61508
KLD2-FBPS-1.12.220
Fieldbus Power Supply
Output: 12 … 13 V/220 mA, For battery or solar-powered applications, For demanding environmental conditions , Installation in Zone 2/Class I, Div. 2, For FOUNDATION Fieldbus H1
We are specialized in intelligent instruments, including : Transmitters, Flowmeters, Analyzers,Communicators, Safety Barriers, Sensors,Gas Detectors, PLC(DCS), Multimeters, Calibrators, Communicators, Recorder, Inverters, Positioners, Valves, Soft Starters, Circuit Breakers, Contactors, Rail Switches, Power Supply, HMI, Terminal Block, Relay etc.