Pepperl+Fuchs KFD2-VR2-Ex1.500M Voltage Repeaters


Features

Voltage Repeater KFD2-VR2-Ex1.500M

1-channel isolated barrier
24 V DC supply (Power Rail)
Voltage input 0 mV … ± 500 mV
Voltage output 0 mV … ± 500 mV
Selectable up/downscale sensor breakage detection
Technical data of Pepperl+Fuchs KFD2-VR2-Ex1.500M Voltage Repeaters

Product Description of Pepperl+Fuchs KFD2-VR2-Ex1.500M Voltage Repeaters

Transmission range 0 mV … ± 500 mV

General specifications of Pepperl+Fuchs KFD2-VR2-Ex1.500M Voltage Repeaters

Signal type Analog input

Supply of Pepperl+Fuchs KFD2-VR2-Ex1.500M Voltage Repeaters

Connection Power Rail or terminals 14+, 15-
Rated voltage 19 … 30 V DC
Ripple within the supply tolerance
Rated current ≤ 11 mA
Power dissipation/power consumption 0.3 W max.

Input of Pepperl+Fuchs KFD2-VR2-Ex1.500M Voltage Repeaters

Connection side field side
Connection terminals 4+, 5-
Input resistance min. 20 MΩ
Transmission range -500 … 500 mV
Offset voltage/current ≤ 5 µV / ≤ 5 nA
Line fault detection 1.3 µA

Output of Pepperl+Fuchs KFD2-VR2-Ex1.500M Voltage Repeaters

Connection side control side
Connection terminals 7+, 8-
Load Accuracy figures for infinite load impedance. Additional 0.03 % of span for a load resistance of 10 kΩ
Voltage -500 … 500 mV
Fault signal sensor breakage: > +500 mV (upscale), < -500 mV (downscale)
Output resistance max. 3 Ω

Transfer characteristics of Pepperl+Fuchs KFD2-VR2-Ex1.500M Voltage Repeaters

Cut-off frequency 350 Hz (-3 dB)
Deviation
After calibration at 20 °C (68 °F):
± 30 µV up to ± 100mV/± 0.03 % of the span up to +500 mV/± 0.03 % of the span up to -500 mV
Influence of ambient temperature ± 10 µV/K (typical ± 5 µV/K)
Absolute < 0.25 K at 30 V voltage supply
Rise time ≤ 1 ms

Galvanic isolation of Pepperl+Fuchs KFD2-VR2-Ex1.500M Voltage Repeaters

Output/power supply functional insulation, rated insulation voltage 50 V AC

Indicators/settings of Pepperl+Fuchs KFD2-VR2-Ex1.500M Voltage Repeaters

Display elements LED
Control elements DIP-switch
Configuration via DIP switches
Labeling space for labeling at the front

Directive conformity of Pepperl+Fuchs KFD2-VR2-Ex1.500M Voltage Repeaters

Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)

Conformity of Pepperl+Fuchs KFD2-VR2-Ex1.500M Voltage Repeaters

Electromagnetic compatibility NE 21:2006
Degree of protection IEC 60529:2001
Protection against electrical shock UL 61010-1

Ambient conditions of Pepperl+Fuchs KFD2-VR2-Ex1.500M Voltage Repeaters

Ambient temperature -20 … 60 °C (-4 … 140 °F)

Mechanical specifications of Pepperl+Fuchs KFD2-VR2-Ex1.500M Voltage Repeaters

Degree of protection IP20
Connection screw terminals
Mass approx. 125 g
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001

Data for application in connection with hazardous areas of Pepperl+Fuchs KFD2-VR2-Ex1.500M Voltage Repeaters

EU-Type Examination Certificate BASEEFA 06 ATEX 0040
Marking Ex-Hexagon II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C ≤ Tamb ≤ 60 °C) , [circuit(s) in zone 0/1/2]
Voltage 5.5 V DC
Current 2.4 mA
Power 3.3 mW
Supply
Maximum safe voltage 250 V (Attention! The rated voltage can be lower.)
Certificate BASEEFA 09 ATEX 0219X
Marking Ex-Hexagon II 3G Ex ec IIC T4 Gc
Galvanic isolation
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012

International approvals of Pepperl+Fuchs KFD2-VR2-Ex1.500M Voltage Repeaters

UL approval
Control drawing 116-0334 (cULus)
IECEx approval
IECEx certificate IECEx BAS 06.0011
IECEx BAS 09.0103X
IECEx marking [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Ex ec IIC T4 Gc

General information of Pepperl+Fuchs KFD2-VR2-Ex1.500M Voltage Repeaters

Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Accessories of Pepperl+Fuchs KFD2-VR2-Ex1.500M Voltage Repeaters

Optional accessories – power feed module KFD2-EB2(.R4A.B)(.SP)
– universal power rail UPR-03(-M)(-S)
– profile rail K-DUCT-BU(-UPR-03)

Classifications of Pepperl+Fuchs KFD2-VR2-Ex1.500M Voltage Repeaters

System Classcode
ECLASS 11.0 27210120
ECLASS 10.0.1 27210120
ECLASS 9.0 27210120
ECLASS 8.0 27210120
ECLASS 5.1 27210120
ETIM 8.0 EC002653
ETIM 7.0 EC002653
ETIM 6.0 EC002653
ETIM 5.0 EC001485

UNSPSC 12.1 32101514

Similar Models of Pepperl+Fuchs KFD2-VR2-Ex1.500M Voltage Repeaters

KFD2-VR-Ex1.18
Voltage Repeater
1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input 0 V … 12 V, Voltage output 0 V … 12 V, Transfer direction: to the control system
KFD2-VR-Ex1.19
Voltage Repeater
1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input -10 V … 10 V, Voltage output -10 V … 10 V, Transfer direction: to the control system
KFD2-VR2-Ex1.50M
Voltage Repeater
1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input 0 mV … ± 50 mV, Voltage output 0 mV … ± 50 mV, Selectable up/downscale sensor breakage detection, Transfer direction: to the control system
KFD2-VR4-Ex1.26
Voltage Repeater
1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input 0 V … -20 V, Vibration sensor inputs, Voltage/current field supply, Voltage output 0 V … -20 V, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the control system
HiC2065
Voltage Repeater
1-channel isolated barrier, 24 V DC supply (bus powered), Voltage input 0 mV … ± 50 mV, Voltage output 0 mV … ± 50 mV, Selectable up/downscale sensor breakage detection, Fault output signal, Transfer direction: to the control system

HiC2068
Voltage Repeater
1-channel isolated barrier, 24 V DC supply (bus powered), Voltage input 0 mV … ± 500 mV, Voltage output 0 mV … ± 500 mV, Selectable up/downscale sensor breakage detection, Fault output signal, Transfer direction: to the control system
HiC2095
Voltage Repeater
1-channel isolated barrier, 24 V DC supply (bus powered), Voltage input 0 V … -20 V, Vibration sensor inputs, Voltage/current field supply, Voltage output 0 V … -20 V, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the control system
HiD2096
Voltage Repeater
2-channel isolated barrier, 24 V DC supply (bus powered), Voltage input 0 V … -20 V, Vibration sensor inputs, Voltage/current field supply, Voltage output 0 V … -20 V, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the control system
KFD2-VR-Ex1.12
Voltage Repeater
1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input 0 V … 9 V, Voltage output 0 V … 9 V, Transfer direction: to the control system
KFD2-VR-Ex1.19-Y109129
Voltage Repeater
1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input -10 V … 10 V, Transmission frequency up to 50 kHz, Voltage output -10 V … 10 V, Transfer direction: to the control system
KFD2-VR2-Ex1.500M
Voltage Repeater
1-channel isolated barrier, 24 V DC supply (Power Rail), Voltage input 0 mV … ± 500 mV, Voltage output 0 mV … ± 500 mV, Selectable up/downscale sensor breakage detection, Transfer direction: to the control system