Pepperl+Fuchs KFU8-DWB-1.D Rotation Speed Monitors
Features
Rotation Speed Monitor KFU8-DWB-1.D
1-channel signal conditioner
Universal usage at different power supplies
Dry contact or NAMUR inputs
Input frequency 1 mHz … 12 kHz
2 relay contact outputs
Start-up override
Configurable by keypad
Line fault detection (LFD)
Up to SIL 2 acc. to IEC 61508/IEC 61511
Technical data of Pepperl+Fuchs KFU8-DWB-1.D Rotation Speed Monitors
Product Description of Pepperl+Fuchs KFU8-DWB-1.D Rotation Speed Monitors
48 V AC … 253 V AC/20 V DC … 90 V DC
General specifications of Pepperl+Fuchs KFU8-DWB-1.D Rotation Speed Monitors
Signal type Digital Input
Functional safety related parameters of Pepperl+Fuchs KFU8-DWB-1.D Rotation Speed Monitors
Safety Integrity Level (SIL) SIL 2
Supply of Pepperl+Fuchs KFU8-DWB-1.D Rotation Speed Monitors
Connection terminals 23, 24
Rated voltage 20 … 90 V DC / 48 … 253 V AC 50 … 60 Hz
Rated current approx. 100 mA
Power dissipation/power consumption ≤ 1.8 W ; 2 VA / 1.8 W ; 2 VA
Input of Pepperl+Fuchs KFU8-DWB-1.D Rotation Speed Monitors
Connection side field side
Connection Input I: 2-wire sensor: terminals 1+, 3- three wire sensor: terminals 1+, 2- and 3
input II: terminals 13+, 14- start-up override;
Input I 2- or 3-wire sensor, sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
Open circuit voltage/short-circuit current 22 V / 40 mA
Input resistance 4.7 kΩ
Switching point/switching hysteresis logic 1: > 2.5 mA ; logic 0: < 1.9 mA
Pulse duration > 50 µs
Input frequency 0.001 … 12000 Hz
Line fault detection breakage I ≤ 0.15 mA; short-circuit I > 4 mA
Input II startup override: 1 … 1000 s, adjustable in steps of 1 s
Active/Passive I > 4 mA (for min. 100 ms) / I < 1.5 mA
Open circuit voltage/short-circuit current 18 V / 5 mA
Output of Pepperl+Fuchs KFU8-DWB-1.D Rotation Speed Monitors
Connection side control side
Connection output I: terminals 10, 11, 12
output II: terminals 16, 17, 18
Output I, II signal, relay
Contact loading 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A
Mechanical life 5 x 107 switching cycles
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Indicators/settings of Pepperl+Fuchs KFU8-DWB-1.D Rotation Speed Monitors
Display elements LEDs , display
Control elements Control panel
Configuration via operating buttons
Labeling space for labeling at the front
Directive conformity of Pepperl+Fuchs KFU8-DWB-1.D Rotation Speed Monitors
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EU EN 61010-1:2010
Conformity of Pepperl+Fuchs KFU8-DWB-1.D Rotation Speed Monitors
Electromagnetic compatibility NE 21:2006
Degree of protection IEC 60529:2001
Ambient conditions of Pepperl+Fuchs KFU8-DWB-1.D Rotation Speed Monitors
Ambient temperature -20 … 60 °C (-4 … 140 °F)
Mechanical specifications of Pepperl+Fuchs KFU8-DWB-1.D Rotation Speed Monitors
Degree of protection IP20
Connection screw terminals
Mass 300 g
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Classifications of Pepperl+Fuchs KFU8-DWB-1.D Rotation Speed Monitors
System Classcode
ECLASS 11.0 27210128
ECLASS 10.0.1 27210128
ECLASS 9.0 27210128
ECLASS 8.0 27210190
ECLASS 5.1 27210121
ETIM 8.0 EC002918
ETIM 7.0 EC002918
ETIM 6.0 EC002918
ETIM 5.0 EC002918
Similar Models of Pepperl+Fuchs KFU8-DWB-1.D Rotation Speed Monitors
KFA6-DWB-Ex1.D
Rotation Speed Monitor
1-channel isolated barrier, 230 V AC supply, Dry contact or NAMUR inputs, Input frequency 1 mHz … 5 kHz, 2 relay contact outputs, Start-up override, Configurable by keypad, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508/IEC 61511
KFD2-DWB-1.D
Rotation Speed Monitor
1-channel signal conditioner, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Input frequency 1 mHz … 12 kHz, 2 relay contact outputs, Start-up override, Configurable by keypad, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508/IEC 61511
KFD2-DWB-Ex1.D
Rotation Speed Monitor
1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Input frequency 1 mHz … 5 kHz, 2 relay contact outputs, Start-up override, Configurable by keypad, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508/IEC 61511
KFU8-DW-1.D
Rotation Speed Monitor
Speed monitoring up to 40 kHz, 1 pre-select value with relay output and LED indicator, 2-, 3-, 4-wire and NAMUR sensors as well as rotary encoder connectable, Start-up delay, Menu driven operation via 4 front keys, Construction type: modular terminal housing in Makrolon, System KF
For use in the switch cabinet/switch cabinet module, Rated voltage: 200 … 230 V AC ; 100 … 130 V AC; 50/60 Hz
20 VDC … 30 VDC
KFU8-DWB-1.D
Rotation Speed Monitor
1-channel signal conditioner, Universal usage at different power supplies, Dry contact or NAMUR inputs, Input frequency 1 mHz … 12 kHz, 2 relay contact outputs, Start-up override, Configurable by keypad, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508/IEC 61511, Rated voltage: 20 … 90 V DC / 48 … 253 V AC 50 … 60 Hz
KFA5-DWB-Ex1.D
Rotation Speed Monitor
1-channel isolated barrier, 115 V AC supply, Dry contact or NAMUR inputs, Input frequency 1 mHz … 5 kHz, 2 relay contact outputs, Start-up override, Configurable by keypad, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508/IEC 61511
1-channel signal conditioner, 24 V DC supply, Input for 2- or 3-wire sensors, Input frequency 10 mHz … 50 kHz, Relay contact output, Start-up override and restart inhibit, Configurable by DIP switches and software, Connection via screw terminals
Ordering Models of Pepperl+Fuchs KFU8-DWB-1.D Rotation Speed Monitors
MTL:
MTL3046B,discontinued,replaced by:MTL5541
MTL3042,discontinued,replaced by:MTL5546Y
MTL5053,discontinued,replaced by:MTL5553
MTL5995,discontinued,replaced by:F101-PS
MTL3000 SERIES (200mA)
MTL4041A,discontinued,replaced by:MTL4541A
MTL4041B,discontinued,replaced by:4541B
MTL5042,discontinued,replaced by:MTL5541
MTL5061,discontinued,replaced by:MTL5561
MTL4842,discontinued,replaced by:MTL4852
FP32