MODEL AND SUFFIX CODES

GENERAL

This General Specifications (GS) provides the

hardware specifications of the safety control unit,

which are intelligent parts of the safety control station

(SCS). This product supports both N-IO and FIO.

 HARDWARE SPECIFICATIONS

For the criteria for the installation environment, refer

to “ProSafe-RS Safety Instrumented System Overview

(for Vnet/IP)” (GS 32P01B10-01EN).

l Module Configuration

Power Supply Module (SPW481, SPW482 or

SPW484): 2 modules

Processor Module (SCP461 style S2 or later):

2 modules for dual redundant

configuration

l Processor

MIPS R5000 Processor

l Main Memory Capacity

128 MB

l Memory Protection at Power Failure

Application program is stored in non-volatile memories.

Processor Module Management Information is

stored in the storage memories backed up by a nonrechargeable battery.

The battery’s recommended replacement cycle is

three years when it is used under the average ambient

temperature of 30 °C or less.

l Temperature Adaptability

A fan unit is provided for high temperature use where

the safety control units (S2SC70S-F/S2SC70D-F)

ambient temperature exceeds 40 °C.

l Control Network

Vnet/IP interface: Dual-redundant

l Installation Restrictions

Up to eight I/O modules (for FIO) can be installed to a S2SC70.

For the I/O module (for FIO) installation limitations and notes, refer to “ProSafe-RS Outline of I/O Modules” (GS

32Q06K20-31E).

l Power Requirements

Specify suffix codes.

Voltage: 100 to 120 V AC, 50 or 60 Hz

Voltage: 220 to 240 V AC, 50 or 60 Hz

Voltage: 24 V DC

l Power Consumption

• S2SC70S-S /S2SC70D-S

100 to 120 V AC model: 200 VA

200 to 240 V AC model: 230 VA

24 V DC model: 5.5 A

• S2SC70S-F/S2SC70D-F

100 to 120 V AC model: 240 VA

200 to 240 V AC model: 290 VA

24 V DC model: 7.0 A

l Weight

S2SC70S-S: Approx. 7.9 kg

S2SC70S-F: Approx. 13 kg

S2SC70D-S: Approx. 8.5 kg

S2SC70D-F: Approx. 13 kg

l Mounting

Rack mounting: Rack mount

(S2SC70-S, M5x8 screws)

(S2SC70-F, M5x12 screws)

Insulation bush (accessory)

l Connection

Power Supply: M4 screw terminal connection

Grounding: M4 screw terminal connection

We are specialized in intelligent instruments, including : Transmitters, Flowmeters, Analyzers,Communicators, Safety Barriers, Sensors,Gas Detectors, PLC(DCS), Multimeters, Calibrators, Communicators, Recorder, Inverters, Positioners, Valves, Soft Starters, Circuit Breakers, Contactors, Rail Switches, Power Supply, HMI, Terminal Block, Relay etc.