Safety Barriers

MTL4544 / MTL4544S Repeater Power Supply, 2-Channel, 4–20 mA HART

MTL Safety Barriers

MTL4544 / MTL4544S Repeater Power Supply

ModelMTL4544 MTL4544S

Repeater power supply for 2- or 3-wire 4/20 mA or HART transmitters. Channels: Two; safe-area output: 4–20 mA (MTL4544: load 0–450 Ω at 20 mA; MTL4544S: current sink, 600 Ω max.).

Channels
Two
Transmitter voltage
16.5 V at 20 mA
Transfer accuracy
Better than 15 µA at 20 °C
Current consumption
96 mA at 24 V DC (20 mA signal)

Availability and lead time confirmed on request

Overview

MTL4544 / MTL4544S Repeater Power Supply, 2-Channel, 4–20 mA HART

Description of MTL4544 / MTL4544S Repeater Power Supply, 2-Channel, 4–20 mA HART

MTL4544/S provides fully-floating dc supplies for energising two conventional 2-wire or 3-wire 4/20mA or HART transmitters located in a hazardous area, and repeats the current in other circuits to drive two safe-area loads. For smart transmitters, the unit allows bi-directional transmission of digital communication signals superimposed on the 4/20mA loop current. Alternatively, the MTL4544S acts as a current sink for a safe-area connection rather than driving a current into the load. Separately powered current sources, such as 4-wire transmitters, can be connected but will not support HART communication.

Specification of MTL4544 / MTL4544S Repeater Power Supply, 2-Channel, 4–20 mA HART

See also common specification

Number of channels  Two

Location of transmitter  Zone 0, IIC, T4–6 hazardous area if suitably certified

Div. 1, Group A hazardous location

Safe-area output

Signal range: 4 to 20mA

Under/over-range: 0 to 24mA

Safe-area load resistance (MTL5544)

@ 24mA: 0 to 360Ω

@ 20mA: 0 to 450Ω

Safe-area load (MTLx544S)

Current sink: 600Ω max.

Maximum voltage source: 24V dc

Safe-area circuit output resistance: > 1MΩ

Safe-area circuit ripple

< 50µA peak-to-peak

Hazardous-area input

Signal range:  0 to 24mA (including over-range)

Transmitter voltage:  16.5V at 20mA

Transfer accuracy at 20°c

Better than 15µA

Temperature drift

< 0.8µA/°C

Response time

Settles to within 10% of final value within 50µs

Communications supported

HART (terminals 1 & 2 and 4 & 5 only)

MTL4500 Series Barriers      MTL4544 / MTL4544S Repeater Power Supply, 2-Channel, 4–20 mA HART

MTL4544 / MTL4544S Repeater Power Supply, 2-Channel, 4–20 mA HART

MTL4544 / MTL4544S Repeater Power Supply, 2-Channel, 4–20 mA HART

MTL5521 Solenoid/Alarm Driver, loop-powered, IIC

MTL4544 / MTL4544S Repeater Power Supply, 2-Channel, 4–20 mA HART

MTL4544 / MTL4544S Repeater Power Supply, 2-Channel, 4–20 mA HART

MTL4544 / MTL4544S Repeater Power Supply, 2-Channel, 4–20 mA HART

MTL4544 / MTL4544S Repeater Power Supply, 2-Channel, 4–20 mA HART

Specifications

FunctionRepeater power supply for 2- or 3-wire 4/20 mA or HART transmitters
ChannelsTwo
Safe-area output4–20 mA (MTL4544: load 0–450 Ω at 20 mA; MTL4544S: current sink, 600 Ω max.)
Transmitter voltage16.5 V at 20 mA
Transfer accuracyBetter than 15 µA at 20 °C
Current consumption96 mA at 24 V DC (20 mA signal)
HARTSupported (terminals 1 & 2 and 4 & 5)
Functional safetySIL 2 capable (single device)

Source: MTL (Eaton) data sheet MTLx544/S. Confirm with the manufacturer datasheet before ordering.

Documents

  • DatasheetPDF · on request Request
  • Operating manualPDF · on request Request
  • Certificate copy (with order, where available)PDF · on request Request