Safety Barriers

Pepperl+Fuchs K-System isolated barriers — series photoSeries photo

Representative photo — same series (Pepperl+Fuchs K-System isolated barriers), not the exact model.

Pepperl+Fuchs Safety Barriers

Pepperl+Fuchs KFD2-SCD2-Ex1.LK SMART Current Driver

ModelKFD2-SCD2-Ex1.LK

SMART current driver, 1-channel isolated barrier for I/P converters and valve positioners. Input: 4–20 mA (control side); output: 4–20 mA, load 100–650 Ω; line fault detection: Yes (LFD).

Input
4–20 mA (control side)
Output
4–20 mA, load 100–650 Ω
Line fault detection
Yes (LFD)
Supply
19–30 V DC via Power Rail or terminals 14+, 15-

Availability and lead time confirmed on request

Overview

Pepperl+Fuchs KFD2-SCD2-Ex1.LK SMART Current Driver, 1-Channel Isolated Barrier

Product Features of Pepperl+Fuchs KFD2-SCD2-Ex1.LK SMART Current Driver, 1-Channel Isolated Barrier

– SMART Current Driver KFD2-SCD2-Ex1.LK

– 1-channel isolated barrier

– 24 V DC supply (Power Rail)

– Current output up to 650 Ω load

– HART I/P and valve positioner

– Line fault detection (LFD)

– Accuracy 0.1 %

– Up to SIL 2 acc. to IEC 61508

Specification of Pepperl+Fuchs KFD2-SCD2-Ex1.LK SMART Current Driver, 1-Channel Isolated Barrier

General specifications of Pepperl+Fuchs KFD2-SCD2-Ex1.LK SMART Current Driver, 1-Channel Isolated Barrier

Signal type Analog output

Functional safety related parameters of Pepperl+Fuchs KFD2-SCD2-Ex1.LK SMART Current Driver, 1-Channel Isolated Barrier

Safety Integrity Level (SIL) SIL 2

Supply

Connection Power Rail or terminals 14+, 15-

Rated voltage 19 … 30 V DC

Ripple ≤ 10 %

Rated current ≤ 30 mA at 24 V

Power dissipation ≤ 600 mW at 20 mA and 500 Ω load

Power consumption ≤ 700 mW

Input of Pepperl+Fuchs KFD2-SCD2-Ex1.LK SMART Current Driver, 1-Channel Isolated Barrier

Connection side control side

Connection terminals 7-, 8+, (9+)

Input signal 4 … 20 mA , limited to approx. 30 mA

Input voltage open loop voltage of the control system ≤ 30 V

Voltage drop approx. 6 V at 20 mA

Input resistance field wiring open circuit : > 100 kΩ

field wiring < 50 Ω : > 100 kΩ when using terminals 1 and 2

Output of Pepperl+Fuchs KFD2-SCD2-Ex1.LK SMART Current Driver, 1-Channel Isolated Barrier

Connection side field side

Connection terminals 1+, 2-

terminals 3+, 2- (no short circuit detection)

Voltage ≥ 13 V at 20 mA

Current 4 … 20 mA

Load 100 … 650 Ω , for terminals 1, 2

0 … 550 Ω , for terminals 2, 3

Ripple 20 mV rms

Line fault detection breakage, load > 100 kΩ, short-circuit, load < 50 Ω

Fault indication output of Pepperl+Fuchs KFD2-SCD2-Ex1.LK SMART Current Driver, 1-Channel Isolated Barrier

Output type open collector transistor (internal fault bus)

Transfer characteristics of Pepperl+Fuchs KFD2-SCD2-Ex1.LK SMART Current Driver, 1-Channel Isolated Barrier

Deviation at 20 °C (68 °F), 4 … 20 mA

< 0.1 % of full scale, incl. non-linearity and hysteresis

Influence of ambient temperature < 2 µA/K (-20 … 70 °C (-4 … 158 °F)); < 4 µA/K (-40 … -20 °C (-40 … -4 °F))

Frequency range field side into the control side: bandwidth with 0.5 Vpp signal 0 … 3 kHz (-3 dB)

control side into the field side: bandwidth with 0.5 Vpp signal 0 … 3 kHz (-3 dB)

Rise time 10 to 90 % ≤ 10 ms

Galvanic isolation of Pepperl+Fuchs KFD2-SCD2-Ex1.LK SMART Current Driver, 1-Channel Isolated Barrier

Input/Output basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Input/power supply basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Output/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Indicators/settings of Pepperl+Fuchs KFD2-SCD2-Ex1.LK SMART Current Driver, 1-Channel Isolated Barrier

Display elements LEDs

Labeling space for adhesive label at the front

Directive conformity of Pepperl+Fuchs KFD2-SCD2-Ex1.LK SMART Current Driver, 1-Channel Isolated Barrier

Electromagnetic compatibility

Directive 2014/30/EU EN 61326-1:2013 (industrial locations)

Conformity of Pepperl+Fuchs KFD2-SCD2-Ex1.LK SMART Current Driver, 1-Channel Isolated Barrier

Electromagnetic compatibility NE 21:2017

EN 61326-3-2:2018

Degree of protection IEC 60529

Protection against electrical shock UL 61010-1:2012

Ambient conditions of Pepperl+Fuchs KFD2-SCD2-Ex1.LK SMART Current Driver, 1-Channel Isolated Barrier

Ambient temperature -40 … 70 °C (-40 … 158 °F)

Mechanical specifications of Pepperl+Fuchs KFD2-SCD2-Ex1.LK SMART Current Driver, 1-Channel Isolated Barrier

Degree of protection IP20

Connection screw terminals

Mass approx. 115 g

Dimensions 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , housing type B2

Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001

Power Supply

115/230 V AC supply, Output 24 V DC, 500 mA, Electronic short circuit protection, Power Rail connection

KFD0-SCS-Ex1.55

SMART Current Driver/Repeater

1-channel isolated barrier, 24 V DC supply (loop powered), Current input/output 4 mA … 20 mA, HART I/P or transmitter power supply, Low voltage drop, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508, Rated voltage: loop powered, Explosion protection: Ex protection, Transfer direction: to the field / to the control system

KFD2-CRG2-1.D

Transmitter Power Supply

1-channel signal conditioner, 24 V DC supply (Power Rail), Input 2-wire and 3-wire transmitters and 2-wire current sources, Output 0/4 mA … 20 mA, 2 relay contact outputs, Adjustable energized/de-energized delay, Programmable high/low alarm, Linearization function (max 20 points), Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508/IEC 61511

Pepperl+Fuchs KFD2-SCD2-Ex1.LK SMART Current Driver, 1-Channel Isolated Barrier

KFD2-CRG2-Ex1.D

Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire transmitters and 2-wire current sources, Output 0/4 mA … 20 mA, 2 relay contact outputs, Adjustable energized/de-energized delay, Programmable high/low alarm, Linearization function (max 20 points), Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508/IEC 61511

KFD2-HLC-Ex1.D

HART Loop Converter

1-channel isolated barrier, 24 V DC supply (Power Rail), HART field device input with transmitter power supply, Usable as signal splitter (1 input and several outputs), 3 analog outputs 4 mA … 20 mA, Sink and source mode output, Configurable by keypad

KFD2-HLC-Ex1.D.2W

HART Loop Converter

1-channel isolated barrier, 24 V DC supply (Power Rail), HART field device input with transmitter power supply, Usable as signal splitter (1 input and several outputs), 2 relay contact outputs (change-over contacts), 3 analog outputs 4 mA … 20 mA, Sink and source mode output, Configurable by keypad

KFD2-STC5-1

SMART Transmitter Power Supply

1-channel signal conditioner, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/4 mA … 20 mA current sink/current source, Terminals with test points, Up to SIL 2 acc. to IEC 61508

Pepperl+Fuchs KFD2-SCD2-Ex1.LK SMART Current Driver, 1-Channel Isolated Barrier

KFD2-STC5-1.2O

SMART Transmitter Power Supply

1-channel signal conditioner, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA … 20 mA, current sink/current source, Terminals with test points, Up to SIL 3 acc. to IEC 61508

KFD2-STC5-2

SMART Transmitter Power Supply

2-channel signal conditioner, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/4 mA … 20 mA current sink/current source, Terminals with test points, Up to SIL 2 acc. to IEC 61508

KFD2-STC5-Ex1.2O

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA … 20 mA, current sink/current source, Terminals with test points, Up to SIL 3 acc. to IEC 61508

KFD2-STC5-Ex1.H

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/4 mA … 20 mA current sink/current source, Terminals with test points, High field voltage 17 V DC, Up to SIL 2 acc. to IEC 61508

Pepperl+Fuchs KFD2-SCD2-Ex1.LK SMART Current Driver, 1-Channel Isolated Barrier

KFD2-STC5-Ex2

SMART Transmitter Power Supply

2-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/4 mA … 20 mA current sink/current source, Terminals with test points, Up to SIL 2 acc. to IEC 61508

KFU8-CRG2-1.D

Transmitter Power Supply

1-channel signal conditioner, Universal usage at different power supplies, Input 2-wire and 3-wire transmitters and 2-wire current sources, Output 0/4 mA … 20 mA, 2 relay contact outputs, Adjustable energized/de-energized delay, Programmable high/low alarm, Linearization function (max 20 points), Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508/IEC 61511

KFU8-CRG2-Ex1.D

Transmitter Power Supply

1-channel isolated barrier, Universal usage at different power supplies, Input 2-wire and 3-wire transmitters and 2-wire current sources, Output 0/4 mA … 20 mA, 2 relay contact outputs, Adjustable energized/de-energized delay, Programmable high/low alarm, Linearization function (max 20 points), Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508/IEC 61511

Pepperl+Fuchs KFD2-SCD2-Ex1.LK SMART Current Driver, 1-Channel Isolated Barrier

KFU8-VCR-1

Transmitter Power Supply/Converter

1-channel signal conditioner, Universal usage at different power supplies, Input 2-wire and 3-wire transmitters, current and voltage sources, Current and voltage output, Rated voltage: 19 … 90 V DC / 48 … 253 V AC

KLD2-FBPS-1.25.360

Fieldbus Power Supply

Output: 25 … 27 V/360 mA, For most fieldbus applications, High-power trunk for high device count and long cable lengths, Installation in Zone 2/Class I, Div. 2, For FOUNDATION Fieldbus H1

KFD2-STC5-Ex1

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/4 mA … 20 mA current sink/current source, Terminals with test points, Up to SIL 2 acc. to IEC 61508

KCD2-STC-1.2O

SMART Transmitter Power Supply

1-channel signal conditioner, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA … 20 mA or 0/1 V … 5 V, Terminal blocks with test sockets, Up to SIL 2 acc. to IEC 61508

KCD2-STC-Ex1

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA … 20 mA or 1 V … 5 V, Housing width 12.5 mm, Up to SIL 2 acc. to IEC 61508

KCD2-STC-Ex1.2O

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA … 20 mA or 0/1 V … 5 V, Terminal blocks with test sockets, Up to SIL 2 acc. to IEC 61508

KCD2-STC-Ex1.ES

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA … 20 mA or 1 V … 5 V, Sink or source mode, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 3 acc. to IEC 61508

Pepperl+Fuchs KFD2-SCD2-Ex1.LK SMART Current Driver, 1-Channel Isolated Barrier

KCD2-STC-Ex1.SP

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA … 20 mA or 1 V … 5 V, Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 2 acc. to IEC 61508

KFA6-STR-1.24.4

Power Supply

115/230 V AC supply, Output 24 V DC, 4 A, Fused output, Power Rail connection

KFD0-CS-1.50

Repeater

1-channel signal conditioner, 24 V DC supply (loop powered), Current input/output 4 mA … 20 mA, transmitter power supply, Accuracy 0.1 %, Reverse polarity protection, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system

KFD0-CS-2.50

Repeater

2-channel signal conditioner, 24 V DC supply (loop powered), Current input/output 4 mA … 20 mA, transmitter power supply, Accuracy 0.1 %, Reverse polarity protection, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system

Pepperl+Fuchs KFD2-SCD2-Ex1.LK SMART Current Driver, 1-Channel Isolated Barrier

KFD0-CS-Ex1.50P

Repeater

1-channel isolated barrier, 24 V DC supply (loop powered), Current input/output 4 mA … 20 mA, transmitter power supply, Accuracy 0.1 %, Reverse polarity protection, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system

KFD0-CS-Ex1.51P

Current Driver/Repeater

1-channel isolated barrier, 24 V DC supply (loop powered), Current input/output 0 mA … 40 mA, I/P or transmitter power supply, Accuracy 1 %, Reverse polarity protection, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system

KFD0-CS-Ex2.50P

Repeater

2-channel isolated barrier, 24 V DC supply (loop powered), Current input/output 4 mA … 20 mA, transmitter power supply, Accuracy 0.1 %, Reverse polarity protection, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system

KFD0-CS-Ex2.51P

Current Driver/Repeater

2-channel isolated barrier, 24 V DC supply (loop powered), Current input/output 0 mA … 40 mA, I/P or transmitter power supply, Accuracy 1 %, Reverse polarity protection, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system

KFD2-STC3-Ex1

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), 2-wire SMART transmitter, Output 4 mA … 20 mA, SMART capable up to 40 kHz (-1dB), Suitable for Honeywell DE protocol, Terminals with test points

KFD2-STC4-Ex2-Y1

SMART Transmitter Power Supply, Output Current Sink

2-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire SMART transmitters, Output 0/4 mA … 20 mA current sink, Terminal blocks with test sockets, Up to SIL 2 acc. to IEC 61508

Pepperl+Fuchs KFD2-SCD2-Ex1.LK SMART Current Driver, 1-Channel Isolated Barrier

KFD2-STC5-Ex1

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/4 mA … 20 mA current sink/current source, Terminals with test points, Up to SIL 2 acc. to IEC 61508

KFD2-STC5-Ex1.2O.H

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA … 20 mA, current sink/current source, Terminals with test points, High field voltage 17 V DC, Up to SIL 3 acc. to IEC 61508

KCD2-STC-Ex1.2O.DE

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA … 20 mA or 0/1 V … 5 V, Terminal blocks with test sockets, Up to SIL 2 acc. to IEC 61508

KCD2-STC-Ex1.2O.ES

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA … 20 mA or 0/1 V … 5 V, Terminal blocks with test sockets, Up to SIL 3 acc. to IEC 61508

KCD2-STC-Ex1.ES.SP

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input for 2-wire SMART transmitters and current sources, Output for 4 mA … 20 mA or 1 V … 5 V, Sink or source mode, Line fault detection (LFD), Housing width 12.5 mm, Connection via spring terminals with push-in connection technology, Up to SIL 3 acc. to IEC 61508

KFD0-CS-2.51P

Current Driver/Repeater

2-channel signal conditioner, 24 V DC supply (loop powered), Current input/output 0 mA … 40 mA, I/P or transmitter power supply, Accuracy 1 %, Reverse polarity protection, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system

KFD0-SCS-1.55

SMART Current Driver/Repeater

1-channel signal conditioner, 24 V DC supply (loop powered), Current input/output 4 mA … 20 mA, HART I/P or transmitter power supply, Low voltage drop, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control system

KFD2-HLC-Ex1.D.4S

HART Loop Converter

1-channel isolated barrier, 24 V DC supply (Power Rail), HART field device input with transmitter power supply, Usable as signal splitter (1 input and several outputs), 4 relay contact outputs (NO contact), 3 analog outputs 4 mA … 20 mA, Sink and source mode output, Configurable by keypad

Pepperl+Fuchs KFD2-SCD2-Ex1.LK SMART Current Driver, 1-Channel Isolated Barrier

KFD2-STC4-Ex1.2O-Y1

SMART Transmitter Power Supply, Output Current Sink

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA … 20 mA, current sink, Terminal blocks with test sockets, Up to SIL 3 acc. to IEC 61508

KFD2-STV4-Ex1-2

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/2 V … 10 V, Terminals with test points, Up to SIL 2 acc. to IEC 61508

KFD2-STV4-Ex1.2O-1

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Signal splitter (1 input and 2 outputs), Dual output 0/1 V … 5 V, Terminal blocks with test sockets, Up to SIL 3 acc. to IEC 61508

KFD2-STV4-Ex2-1

SMART Transmitter Power Supply

2-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire SMART transmitters, Output 0/1 V … 5 V, Terminals with test points, Up to SIL 2 acc. to IEC 61508

KFD2-STV4-Ex2-2

SMART Transmitter Power Supply

2-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire SMART transmitters, Output 0/2 V … 10 V, Terminals with test points, Up to SIL 2 acc. to IEC 61508

KFD2-STV5-Ex1-1

SMART Transmitter Power Supply

1-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire and 3-wire SMART transmitters and 2-wire SMART current sources, Output 0/1 V … 5 V, Terminals with test points, Up to SIL 2 acc. to IEC 61508

KLD2-FBPS-1.12.220

Fieldbus Power Supply

Output: 12 … 13 V/220 mA, For battery or solar-powered applications, For demanding environmental conditions , Installation in Zone 2/Class I, Div. 2, For FOUNDATION Fieldbus H1

Pepperl+Fuchs KFD2-SCD2-Ex1.LK SMART Current Driver, 1-Channel Isolated Barrier

We are specialized in intelligent instruments, including : Transmitters, Flowmeters, Analyzers,Communicators, Safety Barriers, Sensors,Gas Detectors, PLC(DCS), Multimeters, Calibrators, Communicators, Recorder, Inverters, Positioners, Valves, Soft Starters, Circuit Breakers, Contactors, Rail Switches, Power Supply, HMI, Terminal Block, Relay etc.

Specifications

FunctionSMART current driver, 1-channel isolated barrier for I/P converters and valve positioners
Input4–20 mA (control side)
Output4–20 mA, load 100–650 Ω
Line fault detectionYes (LFD)
Supply19–30 V DC via Power Rail or terminals 14+, 15-
Functional safetySIL 2 (SC 3)
Housing20 × 124 × 115 mm (W × H × D), 35 mm DIN rail

Source: Pepperl+Fuchs product page and data sheet KFD2-SCD2-Ex1.LK. Confirm with the manufacturer datasheet before ordering.

Documents

  • DatasheetPDF · on request Request
  • Operating manualPDF · on request Request
  • Certificate copy (with order, where available)PDF · on request Request