MTL5541 Repeater Power Supply
ModelMTL5541
Repeater power supply for 2- or 3-wire 4/20 mA or HART transmitters. Channels: One; safe-area output: 4–20 mA, load 0–450 Ω at 20 mA; transmitter voltage: 16.5 V at 20 mA.
- Channels
- One
- Safe-area output
- 4–20 mA, load 0–450 Ω at 20 mA
- Transmitter voltage
- 16.5 V at 20 mA
- Transfer accuracy
- Better than 15 µA at 20 °C
Availability and lead time confirmed on request
Overview
MTL5541 Repeater Power Supply, 1-Channel, 4–20 mA HART
Description of MTL5541 Repeater Power Supply, 1-Channel, 4–20 mA HART
The MTLx541 provides a fully-floating dc supply for energising a conventional 2- or 3-wire 4/20mA transmitter, which is located in a hazardous area, and repeats the current in another floating circuit to drive a safe-area load. For HART 2-wire transmitters, the unit allows bi-directional communications signals superimposed on the 4/20mA loop current. Alternatively, the MTLx541S acts as a current sink for a safe-area connection rather than driving a current into the load. Separately powered current sources, such as 4-wire transmitters, can be connected but will not support HART communication.
MTL5541 Repeater Power Supply, 1-Channel, 4–20 mA HART
The following guide is for users who require guidance on their choice of isolator for a new installation. For a given application the choice is between DIN-rail mounting (MTL5000/MTL5500 range) and backplane mounting (MTL4000/MTL4500 range) devices.
MTL5541 Repeater Power Supply, 1-Channel, 4–20 mA HART
Analogue Input – 2-wire transmitters, 4-20mA conventional and ‘smart’
DeviceNo. of
channelsOutput to
hazardous areaImportant features
DIN-rail mounting devices of MTL5541 Repeater Power Supply, 1-Channel, 4–20 mA HART
MTL5541116.5V min.
@ 20mACompatible with most smart transmitters
MTL5541A18.6V diodeSeparately powered smart transmitters
MTL5541AS18.6V diode4 wire smart transmitters, current sink output
MTL5541S116.5V min.
@20mACompatible with most smart transmitters, current sink output
MTL5544216.5V min
@ 20mACompatible with most smart transmitters
MTL5544A28.6V diodeSeparately powered smart transmitters
MTL5544AS28.6V diode4 wire smart transmitters, current sink output
MTL5544D116.5V min
@ 20mACompatible with most smart transmitters, repeat output
MTL5544S216.5V min
@ 20mACompatible with most smart transmitters, current sink output
Backplane mounting devices of MTL5541 Repeater Power Supply, 1-Channel, 4–20 mA HART
MTL4541116.5V min
@ 20mACompatible with most smart transmitters
MTL4541A18.6V diodeSeparately powered smart tranmitters
MTL4541P117.6V min
@ 20mAAs MTL4541B but with a higher power output, MTL4041P substitution on legacy backplanes
MTL4541S116.5V min
@ 20mACompatible with most smart transmitters, current sink output
MTL4544216.5V min
@ 20mACompatible with most smart transmitters
MTL4544A28.6V diodeSeparately powered smart transmitters
transducerCompatible with vibration and accelerometer transducers
Analogue Input – thermocouple and mV sources of MTL5541 Repeater Power Supply, 1-Channel, 4–20 mA HART
DeviceNo. of
channelsOutput to
safe areaMain features
DIN-rail mounting devices
MTL557314/20mAConfigurable, built-in CJC, early burnout detection facility
MTL557514/20mAConfigurable, built-in CJC, early burnout detection facility, alarm output
MTL5576-THC24/20mAConfigurable, built-in CJC, also config as 1in 2 out
MTL558110 to ±50mVSelectable upscale or downscale
Backplane mounting devices
MTL457314/20mAConfigurable, built-in CJC, early burnout detection facility
MTL457514/20mAConfigurable, built-in CJC, early burnout detection facility, alarm output
MTL4576-THC24/20mAConfigurable, built-in CJC, also config as 1in 2 out
MTL458110 to ±50mVSelectable upscale or downscale
Analogue Input – 2, 3 and 4-wire RTDs of MTL5541 Repeater Power Supply, 1-Channel, 4–20 mA HART
DeviceNo. of
channelsOutput to
safe areaMain features
DIN-rail mounting devices
MTL557314/20mAConfigurable, many sensor types and ranges
MTL557514/20mAConfigurable, many sensor types and ranges, alarm output
MTL5576-RTD24/20mAConfigurable, also config as 1in 2 out
MTL5582B110 to 400 ohmIndependent selection of 2, 3 or 4-wire RTDs on safe and hazardous area sides
Backplane mounting devices
MTL457314/20mAConfigurable, many sensor types and ranges
MTL457514/20mAConfigurable, many sensor types and ranges, alarm output
MTL4576-RTD24/20mAConfigurable, also config as 1in 2 out
Analogue Output – controller outputs, I/P converters of MTL5541 Repeater Power Supply, 1-Channel, 4–20 mA HART
DeviceNo. of
channelsOutput to
hazardous areaImportant features
DIN-rail mounting devices
MTL554611mA Vmax = 16VSuitable for HART valve positioners, SC & OC LFD
MTL5546Y11mA Vmax = 16VSuitable for HART valve positioners, OC LFD
MTL554921mA Vmax = 16VSuitable for HART valve positioners, SC & OC LFD
MTL5549Y21mA Vmax = 16VSuitable for HART valve positioners, OC LFD
Backplane mounting devices
MTL454611mA Vmax = 16VSuitable for HART valve positioners, SC & OC LFD
MTL4546Y11mA Vmax = 16VSuitable for HART valve positioners, OC LFD
MTL454921mA Vmax = 16VSuitable for HART valve positioners, SC & OC LFD
MTL4549Y21mA Vmax = 16VSuitable for HART valve positioners, OC LFD
Digital Input – switches / proximity detectors of MTL5541 Repeater Power Supply, 1-Channel, 4–20 mA HART
DeviceNo. of
channelsOutput to
safe areaImportant features
DIN-rail mounting devices
MTL551044 x solid stateCan switch +ve or –ve polarity signals
MTL5510B44 x solid stateMult-function selectable
MTL551111 x SPDTSwitch/proximity detector repeater
MTL551322 x solid statedc to 500Hz frequency response
MTL551411 x SPDT
1 x SPDTSwitch/proximity detector repeater
Independent LFD output
MTL5514D12 x SPDTDual output switch/proximity detector repeater
MTL5516C22 x SPDTSwitch/proximity detector repeater
MTL551722 x SPDT
1 x SPDTSwitch/proximity detector repeater
Independent LFD output
Backplane mounting devices
MTL450411 x SPDT
1 x SPDTSwitch/proximity detector repeater
Independent LFD output, de-energise to alarm
MTL451044 x solid stateCan switch +ve or –ve polarity signals
MTL4510B44 x solid stateMult-function selectable
switches +ve, -ve or ac signals
MTL451111 x SPDTSwitch/proximity detector repeater
MTL451322 x solid statedc to 500Hz frequency response
MTL451411 x SPDT
1 x SPDTSwitch/proximity detector repeater
Independent LFD output, energise to alarm
MTL4514D12 x SPDTDual output switch/proximity detector repeater
MTL451622 x SPSTSwitch/proximity detector repeater
MTL4516C22 x SPDTSwitch/proximity detector repeater
MTL451722 x SPST
1 x SPDTSwitch/proximity detector repeater
Independent LFD output
Digital Input – switch/proximity detectors, SIL3 of MTL5541 Repeater Power Supply, 1-Channel, 4–20 mA HART
DeviceNo. of
channelsSignals monitoredImportant features
DIN-rail mounting devices
MTL5501-SR124V logicSafety related, SIL3 certified
Backplane mounting devices
MTL4501-SR124V logicSafety related, SIL3 certified
Digital Output – alarms, LEDs, solenoid valves, etc of MTL5541 Repeater Power Supply, 1-Channel, 4–20 mA HART
DeviceNo. of
channelsOutput to
hazardous areaImportant features
DIN-rail mounting devices
MTL5521112.8V Imax = 48mAIIC gas groups, loop powered
MTL552219.9V Imax = 70mAIIB gas groups, loop powered
MTL5523112.8V Imax = 48mASwitch controlled input, Independent LFD output
MTL5523V112.8V Imax = 48mAVoltage controlled input, Independent LFD output
MTL5524112.8V Imax = 48mASafety override feature, separately powered
MTL552517V Imax = 48mALow power output, loop powered
Backplane mounting devices
Digital Output – switch output to hazardous area of MTL5541 Repeater Power Supply, 1-Channel, 4–20 mA HART
DeviceNo. of
channelsSignals monitoredImportant features
DIN rail mounting devices
MTL55261 or 22 x DPDTSafe-area switch input or loop powered.
2ch or 1ch with 2 outputs
Backplane mounting devices
MTL45261 or 22 x DPDTSafe-area switch input or loop powered.
2ch or 1ch with 2 outputs
Pulse Input – turbine / flowmeters of MTL5541 Repeater Power Supply, 1-Channel, 4–20 mA HART
DeviceNo. of
channelsInput from
hazardous areaImportant features
DIN-rail mounting devices
MTL55321Switch, proximity detector, current pulse, voltage pulseVoltage and current inputs from 2 or 3-wire transmitters
configurable 4-20mA analogue output
MTL554112-wire pulsee.g. 2-wire turbine and vortex flowmeters
Backplane mounting devices
MTL453211mA Vmax = 16VVoltage and current inputs from 2 or 3-wire transmitters
configurable 4-20mA analogue output
MTL454112-wire pulsee.g. 2-wire turbine and vortex flowmeters
Fire / Smoke detectors of MTL5541 Repeater Power Supply, 1-Channel, 4–20 mA HART
DeviceNo. of
channelsOutput to
hazardous areaImportant features
DIN-rail mounting devices
MTL55612Loop powered0–40mA, fire and smoke detectors
Backplane mounting devices
MTL45612Loop powered0–40mA, fire and smoke detector
Signal transfer – safe area to safe area – via hazardous area of MTL5541 Repeater Power Supply, 1-Channel, 4–20 mA HART
Device
pairNo. of
channelsSignal transferredImportant features
DIN-rail mounting devices
MTL5546Y &
MTL5541A14/20mA smartDriver
Receiver
MTL5526 &
MTL5516C2Status signalsDriver, relay output
Receiver, digital output
MTL50511RS232 or RS422Either can be used as receiver or driver
Backplane mounting devices
MTL4546Y &
MTL4541A14/20mA smartDriver
Receiver
MTL4526 &
MTL45162Status signalsDriver, relay output
Receiver, digital output
Trip amplifiers of MTL5541 Repeater Power Supply, 1-Channel, 4–20 mA HART
DeviceNo. of
channelsSignals monitoredImportant features
DIN-rail mounting devices
MTL531414/20mAConfigurable, one or two alarms
PRODUCT LITERATURE of MTL5541 Repeater Power Supply, 1-Channel, 4–20 mA HART
Product CodeDescription
intrinsically safe logo Symbol denotes that the equipment is suitable for use in hazardous area applications.
fsm logo Symbol denotes that the product has been assessed for functional safety applications.
SM45-55-AI SM45-55-AI is FSMFSM Safety Manual – Analogue Input Modules
SM45-55-AO SM45-55-AO is FSMFSM Safety Manual – Analogue Output Modules
SM45-55-BI SM45-55-BI is FSMFSM Safety Manual – Binary Input Modules
SM45-55-MMI SM45-55-MMI is FSMFSM Safety Manual – Machine Monitor Interfaces
SM45-55-SAD SM45-55-SAD is FSMFSM Safety Manual – Solenoid / Alarm Driver Modules
1. Intro of MTL5541 Repeater Power Supply, 1-Channel, 4–20 mA HART
INA4500MTL4500/4600 range Instructions for Safe Use
INM4500/4600MTL4500/4600 range Instruction Manual
MTL4500-5500-ACCBackplanes, Enclosures & Accessories
MTL4500-5500-CSCommon Specifications
MTL4500-5500-DSMTL4500-5500 range Data Set
MTL4525 MTL4525 is intrinsically safe MTL4525 is FSMSwitch operated solenoid driver low power
8. Fire and Smoke of MTL5541 Repeater Power Supply, 1-Channel, 4–20 mA HART
MTL4561 MTL4561 is intrinsically safe MTL4561 is FSM2ch loop-powered, for fire and smoke detectors
9. General of MTL5541 Repeater Power Supply, 1-Channel, 4–20 mA HART
MTL4599Dummy isolator
MTL4599NGeneral purpose feed-through module
Specifications
| Function | Repeater power supply for 2- or 3-wire 4/20 mA or HART transmitters |
|---|---|
| Channels | One |
| Safe-area output | 4–20 mA, load 0–450 Ω at 20 mA |
| Transmitter voltage | 16.5 V at 20 mA |
| Transfer accuracy | Better than 15 µA at 20 °C |
| Response time | Settles within 10 % of final value within 50 µs |
| Supply | 20–35 V DC; 51 mA at 24 V |
| HART | Supported (terminals 1 & 2) |
Source: MTL (Eaton) data sheet MTLx541/S. Confirm with the manufacturer datasheet before ordering.
Documents
- DatasheetPDF · on request Request
- Operating manualPDF · on request Request
- Certificate copy (with order, where available)PDF · on request Request
Downloads will be added after the files have been checked.
Related products
-
MTL5516C Switch/Proximity Detector Interface
MTL5516C: channels Two (this model: One)
-
MTL4544 / MTL4544S Repeater Power Supply
-
MTL4561 Fire and Smoke Detector Interface
-
MTL7778ac / MTL7787+ Shunt-Diode Safety Barriers
Frequently paired with
Often quoted together with MTL MTL5541.